2014-07-01 06:48:102010 FBC
  
 MECHANICAL DENIED
  
 1) SUBMIT TWO COPIES OF MECHANICAL EQUIPMENT SIZING
 CALCULATIONS. FBCR M1401.3
  
 2) PROVIDE AN EQUIPMENT SCHEDULE ON THE PLANS THAT
 MATCHES THE EQUIPMENT SIZING CALCULATIONS. FBCR M1401.3
  
 3) SPECIFY THE DUCT AND GRILL SIZES ON THE PLANS. FBCR
 M1601
  
 4) SHOW COMPLIANCE WITH FBCR M1602.4 FOR BALANCED
 RETURN AIR.
  