| Plan Review Notes For Permit 14050930 |
| Permit Number |
14050930 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2014-07-01 08:47:52 | 2010 FBC / 2008 NEC | | | | | | ELECTRICAL DENIED | | | | | | 1) SUBMIT TWO SETS OF LOAD CALCULATIONS AND PANEL | | | SCHEDULE ON THE PLANS. CITY AMENDMENTS 107.3.5.3 | | | | | | 2) PROVIDE AN ELECTRICAL SERVICE RISER WITH WIRE SIZES, | | | CONDUIT DETAIL AND GROUNDING DETAIL ON THE PLANS. CITY | | | AMENDMENTS 107.3.5.3 | | | | | | 3) SPECIFY THE AIC RATING OF THE ELECTRICAL EQUIPMENT | | | ON THE PLANS. NEC 110.9 | | | | | | 4) AN A/C SERVICE RECEPTACLE OUTLET IS REQUIRED IN AN | | | ACCESSIBLE LOCATION FOR THE EXTERIOR CONDENSING UNIT. | | | NEC 210.63 | | | | | | 5) SHOW COMPLIANCE WITH NEC 406.11 FOR TAMPER-RESISTANT | | | RECEPTACLES. | | | | | | 6) GFCI PROTECTION IS REQUIRED FOR RECEPTACLE OUTLETS | | | LOCATED IN THE GARAGE AND ON THE EXTERIOR OF THE | | | DWELLING. NEC 210.8 | | | | | | 7) SHOW COMPLIANCE WITH NEC 250.94 FOR INTERSYSTEM | | | BONDING. | | | | | | 8) SHOW COMPLIANCE WITH NEC 210.70(3) FOR THE REQUIRED | | | LIGHTING OUTLET IN THE ATTIC. | | | | | | IN ORDER TO REDUCE REVIEW TIME, PLEASE SUBMIT A | | | RESPONSE LETTER INDICATING HOW THE REVIEW ITEMS HAVE | | | BEEN ADDRESSED. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|