Plan Review Notes
Plan Review Notes For Permit 14050930
Permit Number 14050930
Review Stop E
Sequence Number 1
Notes
Date Text
2014-07-01 08:47:522010 FBC / 2008 NEC
  
 ELECTRICAL DENIED
  
 1) SUBMIT TWO SETS OF LOAD CALCULATIONS AND PANEL
 SCHEDULE ON THE PLANS. CITY AMENDMENTS 107.3.5.3
  
 2) PROVIDE AN ELECTRICAL SERVICE RISER WITH WIRE SIZES,
 CONDUIT DETAIL AND GROUNDING DETAIL ON THE PLANS. CITY
 AMENDMENTS 107.3.5.3
  
 3) SPECIFY THE AIC RATING OF THE ELECTRICAL EQUIPMENT
 ON THE PLANS. NEC 110.9
  
 4) AN A/C SERVICE RECEPTACLE OUTLET IS REQUIRED IN AN
 ACCESSIBLE LOCATION FOR THE EXTERIOR CONDENSING UNIT.
 NEC 210.63
  
 5) SHOW COMPLIANCE WITH NEC 406.11 FOR TAMPER-RESISTANT
 RECEPTACLES.
  
 6) GFCI PROTECTION IS REQUIRED FOR RECEPTACLE OUTLETS
 LOCATED IN THE GARAGE AND ON THE EXTERIOR OF THE
 DWELLING. NEC 210.8
  
 7) SHOW COMPLIANCE WITH NEC 250.94 FOR INTERSYSTEM
 BONDING.
  
 8) SHOW COMPLIANCE WITH NEC 210.70(3) FOR THE REQUIRED
 LIGHTING OUTLET IN THE ATTIC.
  
 IN ORDER TO REDUCE REVIEW TIME, PLEASE SUBMIT A
 RESPONSE LETTER INDICATING HOW THE REVIEW ITEMS HAVE
 BEEN ADDRESSED.
  