| 2014-07-01 09:52:46 | 2010 FBC |
| | |
| | DENIED BY BUILDING |
| | |
| | 1) SPECIFY THE WIND DESIGN DATA ON THE PLANS. CITY |
| | AMENDMENTS 107.3.5.3 & FBCR 301.1 |
| | |
| | 2) SPECIFY THE COMPONENT AND CLADDING PRESSURES FOR THE |
| | EXTERIOR DOORS AND WINDOWS ON THE PLANS. FBCR 301.2.1 |
| | |
| | 3) THE EXTERIOR BEARING WALLS OF THIS STRUCTURE DO NOT |
| | HAVE A TWO HOUR FIRE RATING AS REQUIRED FOR TYPE III-B |
| | CONSTRUCTION. IT IS TYPE V-B PER FBC 602. PLEASE |
| | CORRECT. |
| | |
| | 4) SPECIFY THE REQUIRED TRUSS (LIVE AND DEAD) DESIGN |
| | LOADS ON THE PLANS. FBCR 301.6 AND R801.2 |
| | |
| | 5) SUBMIT TWO SETS OF ENERGY CALCULATIONS FOR THE |
| | DWELLING. FBC ENERGY 401.2 |
| | |
| | 6) SPECIFY THE ROOF SHEATHING THAT WILL BE INSTALLED ON |
| | THE PLANS. |
| | |
| | 7) SHOW COMPLIANCE WITH FBCR 803.2.3.1 FOR FASTENING OF |
| | ROOF SHEATHING. |
| | |
| | 8) SHOW COMPLIANCE WITH FBCR 806 FOR ROOF VENTILATION. |
| | |
| | 9) PROVIDE A BUCK DETAIL FOR THE 9' X 7' OVERHEAD |
| | GARAGE DOOR ON THE PLAN. FBCR 612.10.2.1 |
| | |
| | 10) PROVIDE A BUCK DETAIL FOR THE SIDE SWING DOORS ON |
| | THE PLAN. FBCR 612.10.2.1 |
| | |
| | 11) SPECIFY THE ANCHORS THAT WILL BE USED TO ATTACH THE |
| | DOUBLE 2 X 10 BEAM TO THE STRUCTURE AT THE FRONT PORCH. |
| | FBCR 301.1 |
| | |
| | 12) SPECIFY THE ANCHORS THAT WILL BE USED TO ATTACH THE |
| | DOUBLE 2 X 12 BEAM TO THE STRUCTURE AT BEDROOM #1. FBCR |
| | 802.1.9 ( A GIRDER TRUSS COULD BE USED) |
| | |
| | 13) SPECIFY ALL OF THE CONNECTORS THAT WILL BE USED ON |
| | THE FRAMED GABLE WALL SHOWN IN DETAIL S-6 ON SHEET |
| | S-02. FBCR 301.1 |
| | |
| | 14) THE SIMPSON MST 36 STRAP SHOWN IN DETAIL S-5 ON |
| | SHEET S-02 DOES NOT HAVE ANY LATERAL LOAD RESISTANCE |
| | AND THE TRUSS CLIP IS NOT IDENTIFIED. PROVIDE A TRUSS |
| | ANCHOR/CONNECTOR SCHEDULE. FBCR 802.1.9 |
| | |
| | 15) SUBMIT PRODUCT APPROVALS FOR ALL OF THE CONNECTORS |
| | AS REQUIRED BY DCA RULE 9N-3 OR SPECIFY THE FLORIDA OR |
| | MIAMI-DADE PRODUCT APPROVAL NUMBERS IN THE |
| | ANCHOR/CONNECTOR SCHEDULE. |
| | |
| | 16) SHOW THAT THE DOOR FROM THE GARAGE TO THE RESIDENCE |
| | COMPLIES WITH FBCR 302.5.1. |
| | |
| | 17) NO INFORMATION IS PROVIDED ON THE PLANS FOR THE |
| | INTERIOR DOORS. PLEASE PROVIDE A DOOR SCHEDULE. CITY |
| | AMENDMENTS 107. |
| | |
| | 18) SHOW COMPLIANCE WITH FBCR 310.1 FOR EMERGENCY |
| | ESCAPE AND RESCUE OPENINGS IN THE SLEEPING ROOMS. |
| | |
| | 19) SUBMIT TWO COPIES OF PRODUCT APPROVALS FOR THE |
| | EXTERIOR DOORS AND WINDOWS, THE ASPHALT ROOF SHINGLES |
| | AND THE OVERHEAD GARAGE DOOR. DCA RULE 9N-3 |
| | |
| | 20) THE PRODUCT APPROVALS ARE REQUIRED TO BE REVIEWED |
| | AND APPROVED IN WRITING BY THE DESIGNER OF RECORD FOR |
| | THE PROJECT. |
| | |
| | 21) IN ORDER TO REDUCE PLAN REVIEW TIME, PLEASE SUBMIT |
| | A RESPONSE LETTER INDICATING HOW EACH OF THE REVIEW |
| | COMMENTS HAS BEEN ADDRESSED. |
| | |