Plan Review Notes
Plan Review Notes For Permit 14050930
Permit Number 14050930
Review Stop B
Sequence Number 1
Notes
Date Text
2014-07-01 09:52:462010 FBC
  
 DENIED BY BUILDING
  
 1) SPECIFY THE WIND DESIGN DATA ON THE PLANS. CITY
 AMENDMENTS 107.3.5.3 & FBCR 301.1
  
 2) SPECIFY THE COMPONENT AND CLADDING PRESSURES FOR THE
 EXTERIOR DOORS AND WINDOWS ON THE PLANS. FBCR 301.2.1
  
 3) THE EXTERIOR BEARING WALLS OF THIS STRUCTURE DO NOT
 HAVE A TWO HOUR FIRE RATING AS REQUIRED FOR TYPE III-B
 CONSTRUCTION. IT IS TYPE V-B PER FBC 602. PLEASE
 CORRECT.
  
 4) SPECIFY THE REQUIRED TRUSS (LIVE AND DEAD) DESIGN
 LOADS ON THE PLANS. FBCR 301.6 AND R801.2
  
 5) SUBMIT TWO SETS OF ENERGY CALCULATIONS FOR THE
 DWELLING. FBC ENERGY 401.2
  
 6) SPECIFY THE ROOF SHEATHING THAT WILL BE INSTALLED ON
 THE PLANS.
  
 7) SHOW COMPLIANCE WITH FBCR 803.2.3.1 FOR FASTENING OF
 ROOF SHEATHING.
  
 8) SHOW COMPLIANCE WITH FBCR 806 FOR ROOF VENTILATION.
  
 9) PROVIDE A BUCK DETAIL FOR THE 9' X 7' OVERHEAD
 GARAGE DOOR ON THE PLAN. FBCR 612.10.2.1
  
 10) PROVIDE A BUCK DETAIL FOR THE SIDE SWING DOORS ON
 THE PLAN. FBCR 612.10.2.1
  
 11) SPECIFY THE ANCHORS THAT WILL BE USED TO ATTACH THE
 DOUBLE 2 X 10 BEAM TO THE STRUCTURE AT THE FRONT PORCH.
 FBCR 301.1
  
 12) SPECIFY THE ANCHORS THAT WILL BE USED TO ATTACH THE
 DOUBLE 2 X 12 BEAM TO THE STRUCTURE AT BEDROOM #1. FBCR
 802.1.9 ( A GIRDER TRUSS COULD BE USED)
  
 13) SPECIFY ALL OF THE CONNECTORS THAT WILL BE USED ON
 THE FRAMED GABLE WALL SHOWN IN DETAIL S-6 ON SHEET
 S-02. FBCR 301.1
  
 14) THE SIMPSON MST 36 STRAP SHOWN IN DETAIL S-5 ON
 SHEET S-02 DOES NOT HAVE ANY LATERAL LOAD RESISTANCE
 AND THE TRUSS CLIP IS NOT IDENTIFIED. PROVIDE A TRUSS
 ANCHOR/CONNECTOR SCHEDULE. FBCR 802.1.9
  
 15) SUBMIT PRODUCT APPROVALS FOR ALL OF THE CONNECTORS
 AS REQUIRED BY DCA RULE 9N-3 OR SPECIFY THE FLORIDA OR
 MIAMI-DADE PRODUCT APPROVAL NUMBERS IN THE
 ANCHOR/CONNECTOR SCHEDULE.
  
 16) SHOW THAT THE DOOR FROM THE GARAGE TO THE RESIDENCE
 COMPLIES WITH FBCR 302.5.1.
  
 17) NO INFORMATION IS PROVIDED ON THE PLANS FOR THE
 INTERIOR DOORS. PLEASE PROVIDE A DOOR SCHEDULE. CITY
 AMENDMENTS 107.
  
 18) SHOW COMPLIANCE WITH FBCR 310.1 FOR EMERGENCY
 ESCAPE AND RESCUE OPENINGS IN THE SLEEPING ROOMS.
  
 19) SUBMIT TWO COPIES OF PRODUCT APPROVALS FOR THE
 EXTERIOR DOORS AND WINDOWS, THE ASPHALT ROOF SHINGLES
 AND THE OVERHEAD GARAGE DOOR. DCA RULE 9N-3
  
 20) THE PRODUCT APPROVALS ARE REQUIRED TO BE REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD FOR
 THE PROJECT.
  
 21) IN ORDER TO REDUCE PLAN REVIEW TIME, PLEASE SUBMIT
 A RESPONSE LETTER INDICATING HOW EACH OF THE REVIEW
 COMMENTS HAS BEEN ADDRESSED.
  
 ROBERT MCDOUGAL