| Date |
Text |
| 2014-06-19 08:43:50 | DATE: 6/19/2014 |
| | PROJECT: PORCH ENCLOSURE |
| | PERMIT#: 14050922 |
| | CODE: 2008 EDITION OF THE NEC |
| | 2010 EDITION OF THE FBC |
| | 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, |
| | ADMINISTRATION, 2012 FBC SUPPLEMENTS. |
| | |
| | 1ST ELECTRICAL PLAN REVIEW |
| | ACTION: DENIED |
| | |
| | 1) CIRCUIT FOR NEW AIR CONDITIONER NOT SHOWN. INDICATE |
| | THE LOCATION OF THE PANEL(S) INTENDED TO FEED THE NEW |
| | A/C. PROVIDE LOAD CALCULATION AND PANEL SCHEDULE. FBC- |
| | 107.3.5.3 |
| | 2) MINIMUM LIGHTING OUTLETS. AT LEAST ONE LIGHTING |
| | OUTLET SHALL BE PROVIDED IN EVERY BATHROOM, HALLWAY, |
| | STAIRWAY, ATTACHED GARAGE, AND DETACHED GARAGE WITH |
| | ELECTRIC POWER, AND TO ILLUMINATE OUTDOOR ENTRANCES. |
| | FBC-R 708.3.5 |
| | 3) ALL ENCLOSED AREAS, OTHER THAN CLOSETS, KITCHENS, |
| | BASEMENTS, GARAGES, HALLWAYS, LAUNDRY AREAS, UTILITY |
| | AREAS, STORAGE AREAS, AND BATHROOMS SHALL HAVE A |
| | MINIMUM OF TWO DUPLEX RECEPTACLE OUTLETS OR ONE DUPLEX |
| | RECEPTACLE OUTLET AND ONE CEILING OR WALL-TYPE LIGHTING |
| | OUTLET. FBC-R 708.3.1 |
| | 4) INDICATE THE EXISTENCE OF SMOKE AND CARBON MONOXIDE |
| | DETECTORS OR INSTALL THEM. REMODELING OF AN EXISTING |
| | STRUCTURE IS REQUIRED TO INCLUDE INTERCONNECTED SMOKE |
| | ALARMS INSIDE AND OUTSIDE EACH SLEEPING AREA. IF THE |
| | RESIDENCE HAS GAS APPLIANCES, AN ATTACHED GARAGE OR A |
| | FIRE PLACE A CARBON MONOXIDE DETECTOR IS REQUIRED |
| | WITHIN TEN FEET OF EACH ROOM USED FOR SLEEPING. 2010 |
| | FBC-R 314, 315 |
| | 5) SEPARATE PERMITS REQUIRED FOR ELECTRICAL DESCRIBED |
| | ABOVE AS WELL AS INCIDENTALS SUCH AS BUT NOT LIMITED TO |
| | SECURITY, AUDIO/VIDEO, CCTV |
| | |
| | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, |
| | 561-805-6717 OR AT [email protected] |
| | |
| | |