| Plan Review Notes For Permit 14050916 |
| Permit Number |
14050916 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2014-05-31 14:10:29 | ELECTRICAL 1ST REVIEW. | | | | | | ACTION: DENIED. | | | | | | CODE: 2010 FBC, 2008 NEC | | | | | | COMMENTS: | | | | | | 1) INDICATE A LOCATION ON THE SITE PLAN FOR THE NEW 150 | | | KVA TRANSFORMER AND NEW PANEL "HA". FBC 107.3.5.1 | | | | | | 2) PROVIDE A PANEL DIRECTORY FOR THE NEW PANEL "HA". | | | NEC 408.4 | | | | | | 3) INDICATE HOW THE SERVICE MAINS WILL BE LABELED. NEC | | | 230.72 | | | | | | |
|