| 2014-08-04 15:16:46 | BUILDING PLAN REVIEW |
| | PERMIT: 14050913 |
| | ADD: 1016 CLARE SUITE # 3 |
| | CONT: RIELLY CONSTRUCTION |
| | TEL: (561)262-6876 |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: MONDAY JUNE 23/ 2014 |
| | ACTION: DENIED |
| | |
| | 1) THE LIFE SAFETY SHEET LS 1.1 DESIGN STANDARDS & CODE |
| | REQUIREMENT HEADING LIST THE BUILDING AS FULLY |
| | SPRINKLERED WITH A NFPA 13 SYSTEM. PLEASE NOTE THAT THE |
| | SPRINKLERS DOES NOT STATE WHAT TYPE OF HEADS ARE |
| | CURRENTLY IN USE. PLEASE REFER TO THE 2010 FBC-B |
| | SECTION 709.1 EXCEPTION #3 THAT WILL GREATLY EFFECT |
| | YOUR DESIGN AND CODE COMPLIANCE. EXCEPTION 3. IN |
| | MINI-WAREHOUSES/SELF-STORAGE BUILDINGS, WALLS USED TO |
| | SEPARATE TENANTS SHALL NOT BE REQUIRED TO HAVE |
| | FIRE-RESISTANCE RATING, PROVIDED A SPRINKLER SYSTEM |
| | MEETING THE REQUIREMENTS OF ORDINARY HAZARD GROUP II AS |
| | DEFINED BY NFPA 13, IS INSTALLED EMPLOYING QUICK |
| | RESPONSE HEADS. |
| | |
| | 2) COMPLIED. |
| | |
| | 3) 2ND REVIEW, RESPONSE INDICATES THE CONTRACTOR WILL |
| | PROVIDE A COST BREAKDOWN OF THE EXPENDITURES ON |
| | ACCISSIBILITY AND ACCESSIBLE ITEMS. NO SUCHDOCUMENTS |
| | WERE SUBMITTED FOR THIS REVIEW. |
| | LS1.1 PLEASE PROVIDE A COST BREAK DOWN WHERE 20% OR |
| | $70.00 DOLLARS IN ACCESSIBLE UPGRADES TO THE BUILDING. |
| | 2010 FL ACCESSIBILITY CODE 202.4.2 ACCESSIBLE FEATURES |
| | IN THE EVENT OF DISPROPORTIONALITY. |
| | WHEN THE COST OF ALTERATIONS NECESSARY TO MAKE THE PATH |
| | OF TRAVEL TO THE ALTERED AREA FULLY ACCESSIBLE IS |
| | DISPROPORTIONATE TO THE COST OF THE OVERALL ALTERATION, |
| | THE PATH OF TRAVEL SHALL BE MADE ACCESSIBLE TO THE |
| | EXTENT THAT IT CAN BE MADE ACCESSIBLE WITHOUT INCURRING |
| | DISPROPORTIONATE COSTS. IN CHOOSING WHICH ACCESSIBLE |
| | ELEMENTS TO PROVIDE, PRIORITY SHOULD BE GIVEN TO THOSE |
| | ELEMENTS THAT WILL PROVIDE THE GREATEST ACCESS, IN THE |
| | FOLLOWING ORDER: (I) AN ACCESSIBLE ENTRANCE; (II) AN |
| | ACCESSIBLE ROUTE TO THE ALTERED AREA; (III) AT LEAST |
| | ONE ACCESSIBLE RESTROOM FOR EACH SEX OR A SINGLE UNISEX |
| | RESTROOM; (IV) ACCESSIBLE TELEPHONES; (V) ACCESSIBLE |
| | DRINKING FOUNTAINS; AND (VI) WHEN POSSIBLE, ADDITIONAL |
| | ACCESSIBLE ELEMENTS SUCH AS PARKING, STORAGE, AND |
| | ALARMS. |
| | |
| | |
| | 4A) PROVISO SHOP DRAWINGS TO FOLLOW< DEFERRED |
| | SUBMITTAL; THE PLANS INDICATE A NEW ELEVATOR, THIS |
| | ELEVATOR WILL NEED TO COMPLY WITH THE 2010 |
| | FBC-ACCESSIBILITY CODE 3001.3 ACCESSIBILITY. |
| | PASSENGER ELEVATORS ARE REQUIRED TO BE ACCESSIBLE BY |
| | THE FLORIDA BUILDING CODE, ACCESSIBILITY. |
| | |
| | 4B) PROVISO SHOP DRAWINGS TO FOLLOW< DEFERRED |
| | SUBMITTAL. NEW WORK. 2010 FBC-B 3001.5.1 EACH NEW |
| | ELEVATOR SHALL COMPLY WITH THE FLORIDA ELEVATOR SAFETY |
| | CODE THAT WAS IN EFFECT AT THE TIME OF RECEIPT OF |
| | APPLICATION FOR THE CONSTRUCTION PERMIT FOR THE |
| | ELEVATOR. NO SUBMITTALS FOR EITHER THE FREIGHT |
| | ELEVATOR. |
| | |
| | 5) SEMI-COMPLIED. THE PLANS SHOW A 1 HOUR RATED WALL ON |
| | THE 1ST FLOOR MISSING ON LS 1.2. 3002.1.1 OPENING |
| | PROTECTIVES. OPENINGS IN HOISTWAY ENCLOSURES SHALL BE |
| | PROTECTED AS REQUIRED IN CHAPTER 7. DOORS ARE (1) HOUR |
| | FIRE RATED NOT SHOWN ON PLANS. |
| | |
| | 6-9) COMPLIED. |
| | |
| | 10) SINCE THIS BUILDING IS CHANGING THE USAGE TYPE FROM |
| | STORAGE TO MINI STORAGE UNITS TTHE PLANS WILL NEED TO |
| | GO TO P B C IMPACT FEE OFFICE FOR ASSESSMENT OF IMPACT |
| | FEES. |
| | |
| | 11) NEW COMMENT, SHEET LS2 NOT CHANGED OUT SHOWING THE |
| | LULA LIFT TO THE 2ND FLOOR NOR THE REQUIRED 1 HOUR |
| | ENCLOSURE AND DOOR. |
| | |
| | 12) NEW COMMENT SHEETS S-2 & S3 HAVE NOT BEEN UPDATED |
| | TO SHOW THE LULA LIFT PENETRATING THE 2ND FLOOR AND |
| | STEEL FRAMING MEMBERS. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |