| Plan Review Notes For Permit 14050913 |
| Permit Number |
14050913 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2014-06-23 15:19:45 | DATE: 6/23/2014 | | | PROJECT: ELITE STORAGE. | | | PERMIT#: 14050913 | | | CODE: 2008 EDITION OF THE NEC | | | 2010 EDITION OF THE FBC | | | 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, | | | ADMINISTRATION, 2012 FBC SUPPLEMENTS. | | | | | | 1ST ELECTRICAL PLAN REVIEW | | | ACTION: DENIED | | | | | | 1) THE BRANCH CIRCUIT FEEDING BATTERY BACKED EMERGENCY | | | AND EXIT LIGHTS SHALL BE THE SAME BRANCH CIRCUIT AS | | | THAT SERVING THE NORMAL LIGHTING IN THE AREA AND | | | CONNECTED AHEAD OF ANY LOCAL SWITCHES NEC 701.11(G) | | | | | | 2) PROVIDE SAFETY LABELING FOR ARC FLASH PROTECTION FOR | | | THE PANEL BOARDS AND MAIN DISCONNECTING MEANS. NEC | | | 110.16, 110.22 | | | | | | 3) ALL ELECTRIC DRINKING FOUNTAINS SHALL BE PROTECTED | | | WITH GROUND-FAULT CIRCUIT-INTERRUPTER PROTECTION. NEC | | | 422.52 | | | | | | 4) PROVIDE SPECS AND CIRCUITRY INFORMATION ON INSTA-HOT | | | FOR 1ST FL BATHROOM. | | | | | | SEPARATE PERMIT APPLICATIONS ACCOMPANIED BY PLANS, AND | | | MANUFACTURER SPECIFICATIONS ARE REQUIRED FOR: LIFT, | | | GENERATOTR, FIRE ALARM, SECURITY, CCTV, NETWORK, | | | DATA/COM, ACCESS CONTROL AND AUDIO/VIDEO. FBC CITY | | | AMEMNDMENTS. | | | | | | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421. | | | 561-805-6717 OR [email protected] | | | |
|