| 2014-06-27 16:40:37 | 2010 FBC |
| | |
| | DENIED BY BUILDING |
| | |
| | 1) THE ARCHITECT IS REQUIRED TO SIGN AND SEAL THE PLANS |
| | THAT ARE SUBMITTED FOR PUBLIC RECORD. FAC 61G1-16.003 |
| | |
| | 2) THE STRUCTURE IS LOCATED IN EXPOSURE CATEGORY C. |
| | PLEASE REVISE PLANS AND ADJUST THE WINDLOAD PRESSURES. |
| | FBCR 301.2.1.4.3 |
| | |
| | 3) SUBMIT TWO SETS OF A DRAINAGE PLAN THAT SHOWS |
| | COMPLIES WITH FBCR 401.3 SURFACE DRAINAGE SHALL BE |
| | DIVERTED TO A STORM SEWER CONVEYANCE OR OTHER APPROVED |
| | POINT OF COLLECTION THAT DOES NOT CREATE A HAZARD. IT |
| | CAN NOT BE DRAINED ONTO ADJACENT LOTS. |
| | |
| | 4) SHOW THAT THE DOOR FROM THE GARAGE TO THE KITCHEN |
| | COMPLIES WITH FBCR 302.5.1. |
| | |
| | 5) SHOW COMPLIANCE WITH FBCR 302.6 FOR DWELLING / |
| | GARAGE FIRE SEPARATION. |
| | |
| | 6) SHOW COMPLIANCE WITH FBCR 806 FOR ROOF VENTILATION. |
| | |
| | 7) SHOW COMPLIANCE WITH FBCR 807.1 FOR ATTIC ACCESS. |
| | |
| | 8) PROVIDE A WALL SECTION THAT SHOWS THE WALL AND ATTIC |
| | INSULATION ( UN-VENTED ATTIC ), ETC. CITY AMENDMENTS |
| | 107.2.1 |
| | |
| | 9) SPECIFY THE LENGTH OF THE OVERHANG AND THE SOFFIT |
| | MATERIAL THAT WILL BE INSTALLED. CITY AMENDMENTS |
| | 107.2.1 AND FBCR 616.1 |
| | |
| | 10) SPECIFY THE MATERIAL THAT WILL BE INSTALLED ON THE |
| | CEILING OF THE LOGGIA. CITY AMENDMENTS 107.2.1 |
| | |
| | 11) SUBMIT TWO COPIES OF THE MANUFACTURER'S |
| | SPECIFICATIONS, LISTING AND INSTALLATION INSTRUCTIONS |
| | FOR THE BUILT-IN BBQ ON THE LOGGIA. FBCR M1901.2 AND |
| | G2408.1. |
| | |
| | 12) SUBMIT TWO COPIES OF THE PRODUCT EVALUATION REPORT |
| | FOR THE SPRAY FOAM INSULATION IF IT IS USED. FBCR 316 |
| | |
| | 13) THE PRODUCT APPROVALS ARE REQUIRED TO BE REVIEWED |
| | AND APPROVED IN WRITING BY THE DESIGNER OF RECORD. CITY |
| | AMENDMENTS 107.3.4.1 |
| | |
| | 14) THE PRODUCT APPROVAL FOR THE WOOD FIXED WINDOWS NOA |
| | NO. 11-1024.07 HAS BEEN SUPERSEDED BY NOA NO. |
| | 14-0402.02. PLEASE SUBMIT THE CURRENT NOA. DCA RULE |
| | 9N-3 |
| | |
| | 15) THE DRAWINGS THAT WERE SUBMITTED FOR THE FIBERGLASS |
| | SWING DOOR AT THE GARAGE WERE NOT SHRUNK TO FIT ON AN |
| | 8" X 11" PAGE AND SOME OF THE INFORMATION WAS CUT OFF. |
| | PLEASE PROVIDE NEW PAGES WITH COMPLETE INFORMATION. DCA |
| | RULE 9N-3 AND CITY AMENDMENTS 107.2.1 |
| | |
| | 16) PLEASE PROVIDE A RESPONSE LETTER THAT INDICATES HOW |
| | EACH OF THE REVIEW ITEMS WAS ADDRESSED. THIS WILL HELP |
| | TO REDUCE PLAN REVIEW TIME. |
| | |