| 2014-05-25 10:15:21 | PLUMBING PLAN REVIEW |
| | PERMIT: 14050851 |
| | ADD: 777 S FLAGLER DR. SUITE # 900 W |
| | CONT: FISHER |
| | TEL: (561)691-4716 |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: SUNDAY MAY 25 TH/ 2014 |
| | ACTION: DENIED |
| | |
| | 1A) SHEET P1.1 NOTE # 3 SHOWS THE USE OF AN AIR |
| | ADMITTANCE VALVE, PLEASE PROVIDE HOW MANY FLOORS ARE |
| | LOCATED ABOVE THIS SUITE AND SHOW COMPLIANCE WITH 2010 |
| | FBC-PLUMBING 917.3.1 LOCATION OF BRANCH. THE HORIZONTAL |
| | BRANCH DRAIN SHALL CONNECT TO THE DRAINAGE STACK OR |
| | BUILDING DRAIN A MAXIMUM OF FOUR BRANCH INTERVALS FROM |
| | THE TOP OF THE STACK. |
| | |
| | 1B) PLEASE ALSO CONSIDER RETURN AIR PLENUMS AS FOUND ON |
| | SHEETS M2.1, PLEASE REVIEW 2010 FBC-PLUMBING SECTION |
| | 17.8 PROHIBITED INSTALLATIONS. AIR ADMITTANCE VALVES |
| | SHALL NOT BE LOCATED IN SPACES UTILIZED AS SUPPLY OR |
| | RETURN AIR PLENUMS. |
| | |
| | 2) SHEET P1.1 NOTE # 11 INDICATES THE USE OF A NEW |
| | DRINKING FOUNTAIN BUT THE SHEET DOES NOT SHOW A WASTE |
| | TO THE SANITARY SEWER. THE 2010 FBC-PLUMBING TABLE |
| | 709.1 DRINKING FOUNTAINS 1/2 DFU'S AND MINIMUM TRAP |
| | SIZE OF 1 1/4 INCH. |
| | |
| | 3) 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. DRINKING |
| | FONTAINS UNDER THE FL ACCESSIBILITY CODE ARE REQUIRED |
| | TO COMPLY WITH 211.2 MINIMUM NUMBER. |
| | NO FEWER THAN TWO DRINKING FOUNTAINS SHALL BE PROVIDED. |
| | ONE DRINKING FOUNTAIN SHALL COMPLY WITH 602.1 THROUGH |
| | 602.6 AND ONE DRINKING FOUNTAIN SHALL COMPLY WITH |
| | 602.7. |
| | EXCEPTION: WHERE A SINGLE DRINKING FOUNTAIN COMPLIES |
| | WITH 602.1 THROUGH 602.6 AND 602.7, IT SHALL BE |
| | PERMITTED TO BE SUBSTITUTED FOR TWO SEPARATE DRINKING |
| | FOUNTAINS. |
| | NO MONIES HAVE BEEN SPENT UNDER THE DIPROPORTIONATE |
| | COST 202.4.1. |
| | |