Plan Review Notes
Plan Review Notes For Permit 14050798
Permit Number 14050798
Review Stop B
Sequence Number 1
Notes
Date Text
2014-05-24 10:38:43BUILDING PLAN REVIEW
 PERMIT: 14050798
 ADD: 1793 PALM BEACH LAKES # W409
 CONT: TBD
 TEL: (561)348-4805
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: SAT. MAY 24/ 2014
 ACTION: DENIED
  
 1) ARCHITECTURAL SHEETS STAMPED NOT SIGNED BY THE
 DESIGNER OF RECORD. PLANS, SPECIFICATIONS, REPORTS OR
 OTHER DOCUMENTS PREPARED BY THE DESIGN PROFESSIONAL AND
 BEING FILED FOR PUBLIC RECORD SHALL HAVE THE SIGNATURE
 AND SEAL OF THE DESIGN PROFESSIONAL AFFIXED TO THE
 DOCUMENT.
 FL ADMIN CODE 61G16.003 ARCHITECTS
  
 2) ELECTRICAL SHEETS STAMPED NOT SIGNED BY THE DESIGNER
 OF RECORD. PLANS, SPECIFICATIONS, REPORTS OR OTHER
 DOCUMENTS PREPARED BY THE DESIGN PROFESSIONAL AND BEING
 FILED FOR PUBLIC RECORD SHALL HAVE THE SIGNATURE AND
 SEAL OF THE DESIGN PROFESSIONAL AFFIXED TO THE
 DOCUMENT.
 FL ADMIN CODE 61G15-23.002 ENGINEERS
 EFFECTIVE DATE 05/06/2009
  
 3) SHEET A1.1 THE OCCUPANCY LOAD FOR THIS TENANT IS 59,
 2010 FBC-B TABLE 1015.1 REQUIRES 2 EXITS FOR A OCCUPANT
 LOAD GREATER THAN 49 FOR A MERCANTILE OCCUPANCY. PLEASE
 REVIEW THE CODE REQUIREMENTS FOR EXITING THROUGH A
 STORE ROOM, MISSING THE REQUIREMENT # 4, AISLE DEFINED
 BY FULL- OR PARTIAL-HEIGHT FIXED WALLS OR SIMILAR
 CONSTRUCTION .
 2010 FBC-B 1014.2 EGRESS THROUGH INTERVENING SPACES.
 EGRESS THROUGH INTERVENING SPACES SHALL COMPLY WITH
 THIS SECTION.
 4) EXCEPTION # 2
 2.1 MEANS OF EGRESS ARE NOT PROHIBITED THROUGH
 STOCKROOMS IN GROUP M OCCUPANCIES WHEN ALL OF THE
 FOLLOWING ARE MET:
 2.1. THE STOCK IS OF THE SAME HAZARD CLASSIFICATION AS
 THAT FOUND IN THE MAIN RETAIL AREA;
 2. .NOT MORE THAN 50 PERCENT OF THE EXIT ACCESS IS
 THROUGH THE STOCKROOM;
 2.3. THE STOCKROOM IS NOT SUBJECT TO LOCKING FROM THE
 EGRESS SIDE; AND
 2.4. THERE IS A DEMARCATED, MINIMUM 44-INCH-WIDE (1118
 MM) AISLE DEFINED BY FULL- OR PARTIAL-HEIGHT FIXED
 WALLS OR SIMILAR CONSTRUCTION THAT WILL MAINTAIN THE
 REQUIRED WIDTH AND LEAD DIRECTLY FROM THE RETAIL AREA
 TO THE EXIT WITHOUT OBSTRUCTIONS.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  