| Plan Review Notes For Permit 14050789 |
| Permit Number |
14050789 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2014-07-09 10:02:34 | DATE: 7/9/2014 | | | PROJECT: BURGER KING | | | PERMIT#: 1405789 | | | CODE: 2008 EDITION OF THE NEC | | | 2010 EDITION OF THE FBC | | | 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, | | | ADMINISTRATION, 2012 FBC SUPPLEMENTS. | | | 2ND ELECTRICAL PLAN REVIEW | | | ACTION: PROVISO | | | | | | 1)ALL EXTERIOR LIGHTING NOT EXEMPTED BY FBC 505.1 SHALL | | | HAVE AUTOMATIC CONTROLS TO TURN OFF AT DAYLIGHT OR WHEN | | | NOT REQUIRED. CONTROLS SHALL BE PHOTOSENSOR & TIME | | | CLOCK OR ASTRONOMICAL TIME SWITCH. ALL TIME SWITCHES | | | SHALL BE CAPABLE OF RETAINING PROGRAMING DURING A LOSS | | | OF POWER FOR A MINIMUM OF 10 HOURS. FBC-E 505.2.4 | | | | | | 2)THE INTERIOR OF AN UNDERGROUND RACEWAY SHALL BE | | | CONSIDERED A WET LOCATION. ALL CONDUCTORS WITHIN THE | | | RACEWAY SHALL BE LISTED ACCORDINGLY. | | | SUITABILITY FOR INSTALLATION AND USE SHALL BE IN | | | CONFORMITY WITH THE PROVISIONS OF THIS CODE. NEC | | | 110.3(A)(1 THRU 8) | | | | | | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, | | | 561-805-6717 OR [email protected] | | | |
|