| Date |
Text |
| 2014-06-11 08:37:29 | DATE: 6/11/2014 |
| | PROJECT: LINCOLN TOWER CONDO, COOLING TOWER. |
| | PERMIT#: 14050778 |
| | CODE: 2008 EDITION OF THE NEC |
| | 2010 EDITION OF THE FBC |
| | 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, |
| | ADMINISTRATION, 2012 FBC SUPPLEMENTS. |
| | |
| | ELECTRICAL PLAN REVIEW |
| | |
| | 1ST REVIEW |
| | ACTION: DENIED |
| | |
| | 1) CLARIFY SCOPE OF ELECTRICAL WORK. NOTES DISCUSS THE |
| | DEMOLITION OF LIGHTING, CONDUIT AND WIRE. PLEASE |
| | INDICATE ON FLOOR PLAN THE SPECIFIC ITEMS TO BE REMOVED |
| | AND OR REPLACED. INDICATE SPECIFICALLY WHAT IS EXISTING |
| | TO REMAIN AND WHAT IS PROPOSED TO BE NEW. INDICATE |
| | MEATHODS AND MATERIALS TO BE USED IN THE COMPLETION OF |
| | THE PROJECT. FBC 107.2.1 |
| | |
| | 2) MINIMUM PLAN REVIEW CRITERIA. ELECTRICAL: WIRING |
| | SERVICES FEEDERS AND BRANCH CIRCUITS OVERCURRENT |
| | PROTECTION GROUNDING WIRING METHODS AND MATERIALS GFCIS |
| | EQUIPMENT SPECIAL OCCUPANCIES, EMERGENCY SYSTEMS, |
| | COMMUNICATION SYSTEMS, LOW VOLTAGE, LOAD CALCULATIONS, |
| | DESIGN FLOOD ELEVATION. FBC 107.3.5.1.2 ELECTRICAL |
| | |
| | 3) THE BRANCH CIRCUIT FEEDING BATTERY BACKED EMERGENCY |
| | AND EXIT LIGHTS SHALL BE THE SAME BRANCH CIRCUIT AS |
| | THAT SERVING THE NORMAL LIGHTING IN THE AREA AND |
| | CONNECTED AHEAD OF ANY LOCAL SWITCHES. NEC 701.11(G) |
| | |
| | 4) ILLUMINATION OF MEANS OF EGRESS SHALL BE PROVIDED IN |
| | ACCORDANCE WITH THIS SECTION FOR EVERY BUILDING AND |
| | STRUCTURE. FOR THE PURPOSE OF THIS REQUIRMENT, EXIT |
| | ACCESS SHALL INCLUDE ONLY DESIGNATED STAIRS, AISLES, |
| | CORRIDORS, RAMPS, ESCELATORS, WALKWAYS AND EXIT |
| | PASSAGEWAYS LEADING TO A PUBLIC WAY. ADDITIONAL |
| | EMERGENCY BATTERY BACKED LIGHTING IS REQUIRED FOR |
| | ADAQUATE ILLUMINATION OF THE EGRESS PATH. FBC 1006.1.1 |
| | |
| | 5) INDICATE DISCONNECTS WHERE REQUIRED AT A/C EQUIPMENT |
| | ETC.. NEC 440.14 |
| | |
| | 6) GFCI OUTLET REQUIRED AT A/C EQUIPMENT. NEC 210.63 |
| | |
| | 7) THE CALCULATED LOAD OF A FEEDER OR SERVICE SHALL NOT |
| | BE LESS THAN THE SUM OF THE LOADS ON THE BRANCH |
| | CIRCUITS SUPPLIED AS DETERMINED BY PART II OF ARTICLE |
| | 220, AFTER ANY APPLICABLE DEMAND FACTORS PERMITTED BY |
| | PART III OR IV OR REQUIRED BY PART V HAVE BEEN APPLIED. |
| | PROVIDE A CALCULATED LOAD SUMMARY TO VERIFY THE |
| | EXISTING FEEDER IS ADAQUATE TO SERVE THE NEW LOADS. NEC |
| | 220.40 |
| | |
| | 8) INDICATE COMPLIANCE WITH ARITCAL 110.26 IN THE NEC |
| | WHICH REQUIRES THAT SUFFICIENT ACCESS AND WORKING SPACE |
| | SHALL BE PROVIDED AND MAINTAINED ABOUT ALL ELECTRICAL |
| | EQUIPMENT TO PERMIT READY AND SAFE OPERATION AND |
| | MAINTENANCE OF SUCH EQUIPMENT. NEC 110.26 |
| | |
| | 9) PROVIDE SAFETY LABELING FOR FLASH PROTECTION AND FOR |
| | THE PANEL BOARDS AND MAIN DISCONNECTING MEANS. NEC |
| | 110.22, 110.16, 110.22 |
| | |
| | 10) MECHANICAL EQUIPMENT, ELECTRICAL, TRANSFORMER, |
| | TELEPHONE EQUIPMENT, ELEVATOR MACHINE OR SIMILAR ROOMS, |
| | A LISTED SMOKE DETECTOR SHALL BE INSTALLED. |
| | FBC-907.2.18.1 LISTED SINGLE AND MULTIPLE STATION SMOKE |
| | ALARMS COMPLYING WITH UL 217 SHALL BE INSTALLED IN |
| | ACCORDANCE WITH SECTIONS 907.2.11.1 THROUGH 907.2.11.4 |
| | AND NFPA 72 |
| | |
| | 11) ALL COMPONENTS AND CABLES SHALL BE UL LISTED AND |
| | LABELED FOR USE IN THE MANNER INSTALLED. NEC 110.3 |
| | |
| | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421. |
| | 561-805-6717 OR [email protected] |