| 2014-06-13 17:50:13 | BUILDING PLAN REVIEW |
| | PERMIT: 14050759 |
| | ADD: 8100 IBIS BLVD |
| | CONT:THE WEITZ CO. |
| | TEL: (561)686-5511 |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: FRIDAY JUNE 13/ 2014 |
| | ACTION: DENIED |
| | |
| | 1) SHEET AS 103 THE ENLARGED DEMO SITE PLAN. IT APPEARS |
| | THE GOLF PRO-SHOP 1ST FLOOR WILL BE OCCIPIED AND OPEN |
| | FOR THE PUBLIC. IF SO PLEASE PROVIDE WHAT SAFE GAURDS |
| | WILL BE PUT IN PLACE TO INSURE THIER SAFETY ENTERING |
| | AND EXITING THE BUILDING WHILE THE REMAINDER OF THE |
| | SITE IS UNDER CONSTRUCTION. |
| | 2010 FBC-B 3302.1 REMODELING AND ADDITIONS. REQUIRED |
| | EXITS, EXISTING STRUCTURAL ELEMENTS, FIRE PROTECTION |
| | DEVICES AND SANITARY SAFEGUARDS SHALL BE MAINTAINED AT |
| | ALL TIMES DURING REMODELING, ALTERATIONS, REPAIRS OR |
| | ADDITIONS TO ANY BUILDING OR STRUCTURE. |
| | 3302.2 MANNER OF REMOVAL. WASTE MATERIALS SHALL BE |
| | REMOVED IN A MANNER WHICH PREVENTS INJURY OR DAMAGE TO |
| | PERSONS, ADJOINING PROPERTIES. |
| | 3303.2 PEDESTRIAN PROTECTION. THE WORK OF DEMOLISHING |
| | ANY BUILDING SHALL NOT BE COMMENCED UNTIL PEDESTRIAN |
| | PROTECTION IS IN PLACE AS REQUIRED BY THIS CHAPTER. |
| | |
| | 2) THIS SAME SHEET IT APPEARS NO REMODELING WILL TAKE |
| | PLACE ON THE INTERIOR OF THE GOLF PRO-SHOP AND WILL BE |
| | OPEN TO THE PUBLIC, PLEASE PROVIDE A RATED FIRE BARRIER |
| | BETWEEN THE ACTIVE WORK SITE 1ST FLOOR OF THE CLUBHOUSE |
| | AND PRO SHOP. 3306.5 BARRIERS. BARRIERS SHALL BE A |
| | MINIMUM OF 8 FEET (2438 MM) IN HEIGHT AND SHALL BE |
| | PLACED ON THE SIDE OF THE WALKWAY NEAREST THE |
| | CONSTRUCTION. BARRIERS SHALL EXTEND THE ENTIRE LENGTH |
| | OF THE CONSTRUCTION SITE. OPENINGS IN SUCH BARRIERS |
| | SHALL BE PROTECTED BY DOORS WHICH ARE NORMALLY KEPT |
| | CLOSED. |
| | |
| | 3) F] 3309.1 WHERE REQUIRED. |
| | ALL STRUCTURES UNDER CONSTRUCTION, ALTERATION OR |
| | DEMOLITION SHALL BE PROVIDED WITH NOT LESS THAN ONE |
| | APPROVED PORTABLE FIRE EXTINGUISHER IN ACCORDANCE WITH |
| | SECTION 906 AND SIZED FOR NOT LESS THAN ORDINARY HAZARD |
| | AS FOLLOWS: |
| | |
| | 3.1.AT EACH STAIRWAY ON ALL FLOOR LEVELS WHERE |
| | COMBUSTIBLE MATERIALS HAVE ACCUMULATED. |
| | |
| | 3.2.IN EVERY STORAGE AND CONSTRUCTION SHED. |
| | |
| | 3.3.ADDITIONAL PORTABLE FIRE EXTINGUISHERS SHALL BE |
| | PROVIDED WHERE SPECIAL HAZARDS EXIST, SUCH AS THE |
| | STORAGE AND USE OF FLAMMABLE AND COMBUSTIBLE LIQUIDS. |
| | |
| | 4) 3309.2 FIRE HAZARDS. THE PROVISIONS OF THIS CODE AND |
| | THE FLORIDA FIRE PREVENTION CODE SHALL BE STRICTLY |
| | OBSERVED TO SAFEGUARD AGAINST ALL FIRE HAZARDS |
| | ATTENDANT UPON CONSTRUCTION OPERATIONS. |
| | |
| | 5) DURING THE DEMOLITION AS WELL AS THE FONDATION WORK |
| | A THRESHOLD INSPECTOR SHALL BE ON SITE. THRESHOLD |
| | INSPECTION PLAN FL S. S. 553.71(7) " THRESHOLD |
| | BUILDING" MEANING ANY BUILDING WHICH IS GREATER THAN |
| | (3) STORIES OR 50 FT IN HEIGHT, OR WHICH HAS AN |
| | ASSEMBLY OCCUPANCY CLASSIFICATION AS DENIED IN THE |
| | FLORIDA BUILDING CODE WHICH EXCEEDS 5,000 SQ FT IN AREA |
| | AND AN OCCUPANT CONTENT OF GREATER THAN 500 PERSONS. |
| | |
| | 6) 109.3.6.1 THE ENFORCING AGENCY SHALL REQUIRE A |
| | SPECIAL INSPECTOR TO PERFORM STRUCTURAL INSPECTIONS ON |
| | A THRESHOLD BUILDING PURSUANT TO A STRUCTURAL |
| | INSPECTION PLAN PREPARED BY THE ENGINEER OF RECORD. THE |
| | STRUCTURAL INSPECTION PLAN MUST BE SUBMITTED TO THE |
| | ENFORCING AGENCY PRIOR TO THE ISSUANCE OF A BUILDING |
| | PERMIT FOR THE CONSTRUCTION OF A THRESHOLD BUILDING. |
| | THE PURPOSE OF THE STRUCTURAL INSPECTION PLAN IS TO |
| | PROVIDE SPECIFIC INSPECTION PROCEDURES AND SCHEDULES SO |
| | THAT THE BUILDING CAN BE ADEQUATELY INSPECTED FOR |
| | COMPLIANCE WITH THE PERMITTED DOCUMENTS. |
| | |
| | 7) THRESHOLD INSPECTOR: WPB AMENDMENT 109.3.6.2 W.P.B. |
| | CONSTRUCTION SERVICES DEPARTMENT REQUEST FOR THRESHOLD |
| | BUILDINGS A SPECIAL INSPECTOR AS REQUIRED BY FL S S |
| | 553.79(5) FLORIDA STATUTES TO THE MINIMUM INSPECTIONS |
| | REQUIRED BY THIS CODE. A THRESHOLD AGREEMENT MUST BE |
| | SIGNED BY THE THRESHOLD INSPECTOR, CONTRACTOR, OWNERS, |
| | PLEASE CONTACT KEN CONRAD MANAGER OF THE SPECIAL |
| | INSPECTOR PROGRAM AT (561)805-6666 FOR FURTHER |
| | INFORMATION BEFORE THE PERMIT MAY BE ISSUED. |
| | |
| | 8) THRESHOLD BLDG, REQUIRED STATEMENT: W.P.B. AMENDMENT |
| | 110.3.7.4.4 ALL PLANS FOR THE BUILDING WHICH ARE |
| | REQUIRED TO BE SIGNED AND SEALED BY THE ARCHITECT OR |
| | ENGINEER OF RECORD CONTAIN A STATEMENT THAT, TO THE |
| | BEST OF THE ARCHITECT'S PR ENGINEER'S KNOWLEDGE, THE |
| | PLANS AND SPECIFICATIONS COMPLY WITH THE APPLICABLE |
| | FIRE-SAFETY STANDARDS AS DETERMINED BY THE LOCAL |
| | AUTHORITY IN |
| | ACCORDANCE WITH THIS SECTION AND 633 FLORIDA STATUTE. |
| | |
| | 9) PLEASE CALL THE CITY OF WEST PALM BEACH?S AUTOMATED |
| | TELEPHONE INSPECTIONS LINE (561) 805-6700) FOR |
| | IN-PROGRESS INSPECTIONS FOR AUDITING OF JOBSITE |
| | INSPECTIONS. |
| | |
| | 9.1) THE CONTRACTOR WILL PRODUCE A JOB SUMMARY OR |
| | HISTORY FOR THIS TYPE OF CONSTRUCTION. |
| | THIS MAY BE SUBMITTED TO KEN CONRAD BY E-MAIL. KEN |
| | CONRAD: [email protected] |
| | |
| | 9.2) FOR THE SPECIAL INSPECTOR PLEASE PROVIDE A RESUME' |
| | OF INSPECTION EXPERIENCE ON PREVIOUS PROJECT. THE |
| | RESUME' MUST BE ACCOMPANIED BY ALL CERTIFICATES AS |
| | SPECIFIED HEREIN. THE BUILDING OFFICIAL OR HIS DESIGNEE |
| | WILL REVIEW THE RESUME'. AFTER THE RESUME' IS REVIEWED, |
| | AN INTERVIEW WILL BE SCHEDULED. UNDER NO CIRCUMSTANCES |
| | WILL AN INSPECTOR BE INTERVIEWED FOR WORK WITHOUT FIRST |
| | MEETING THE ABOVE CRITERIA. |
| | CONTACT KEN CONRAD |
| | TEL: 561-805-6666 |
| | E-MAIL: [email protected] |
| | |
| | 10) SHEET S.001 STRUCTURAL NOTES 2310 INDICATE A SOILS |
| | REPORT WAS COMPLETED, FOUNDATION SOILS REPORT HD 135558 |
| | BY DUNKLEBURGER ENGINEERING & TESTING PLEASE PROVIDE |
| | SOILS REPORT AS REQUIRED BY SECTION 2010 FBC-B 1803.5.2 |
| | QUESTIONABLE SOIL. |
| | WHERE THE CLASSIFICATION, STRENGTH OR COMPRESSIBILITY |
| | OF THE SOIL IS IN DOUBT OR WHERE A LOAD-BEARING VALUE |
| | SUPERIOR TO THAT SPECIFIED IN THIS CODE IS CLAIMED, THE |
| | BUILDING OFFICIAL SHALL BE PERMITTED TO REQUIRE THAT A |
| | GEOTECHNICAL INVESTIGATION BE CONDUCTED. |
| | |
| | 11) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT |
| | FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL |
| | PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND |
| | A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT |
| | APPLICATION. PLEASE CALL (561)233-5025 FOR MORE |
| | INFORMATION. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| | REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL |
| | LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH |
| | A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE |
| | SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE |
| | FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR |
| | YOUR ANTICIPATED COOPERATION. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |