| Plan Review Notes For Permit 14050711 |
| Permit Number |
14050711 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2014-06-09 14:21:38 | ***PROVISO*** | | | ***ISSUED AT CONTRACTOR'S RISK*** | | | ***REVISION REQUIRED PRIOR TO FIRST INSPECTION*** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | A STRUCTURAL DETAIL BY A DESIGN PROFESSIONAL REQUIRED, | | | FS 471, FS 481. | | | | | | STRUCTURAL DETAIL IS TO INCLUDE WIND DESIGN CRITERIA | | | FBC 1609, FASTENER TYPE, FASTENING PATTERN, NUMBER OF | | | FASTENERS REQUIRED, FASTENER DIAMETER, LENGTH OR | | | MINIMUM EMBEDMENT. | | | |
|