| Plan Review Notes For Permit 14050698 |
| Permit Number |
14050698 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2014-05-19 15:29:50 | 2010 FBC | | | | | | DENIED BY BUILDING | | | | | | 1) THE STRUCTURE IS LOCATED IN A 170 MPH WIND SPEED, | | | THE EXPOSURE CATEGORY IS C, THE MEAN ROOF HEIGHT IS | | | LESS THAN 25 FEET AND THE ROOF SLOPE IS 3/12. THE | | | MAXIMUM DESIGN PRESSURE FROM THE PRODUCT APPROVAL IS | | | TOO LOW FOR THE CORNER AND PERIMETER ROOF AREAS. THE | | | REQUIRED UPLIFT IS -68.0 PSF FOR THE PERIMETER AND | | | -99.8 PSF FOR THE CORNERS. SUBMIT TWO SETS OF RAS 117 | | | CALCULATIONS AS REQUIRED BY NOA NO. 13-0424.14 | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] | | | | | | |
|