Plan Review Notes
Plan Review Notes For Permit 14050689
Permit Number 14050689
Review Stop E
Sequence Number 2
Notes
Date Text
2014-07-23 07:29:132010 FBC / 2008 NEC
  
 DENIED BY ELECTRICAL
  
 EXISTING STORAGE AREA THAT IS BEING CONVERTED TO LIVING
 SPACE SHALL COMPLY WITH THE FOLLOWING:
  
 1) PROVIDE LOAD CALCULATIONS AND A PANEL SCHEDULE FOR
 THE EXISTING 60 AMP PANEL. CITY AMENDMENTS 107.2.1 AND
 NEC 220.40
  
 2) COMPLY WITH NEC 210.52 (A) FOR RECEPTACLE OUTLET
 SPACING.
  
 3) COMPLY WITH NEC 210.70 FOR REQUIRED LIGHTING
 OUTLETS.
  
 4) SHOW COMPLIANCE WITH FBC 210.12 FOR ARC-FAULT
 CIRCUIT-INTERRUPTER PROTECTION (AFCI).
  
 5) SHOW COMPLIANCE WITH FBC 406.11 FOR TAMPER-RESISTANT
 RECEPTACLES.
  
 6) SHOW COMPLIANCE WITH FBCR 314.3.1 FOR SMOKE ALARMS.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]