| Plan Review Notes For Permit 14050689 |
| Permit Number |
14050689 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2014-07-23 07:29:13 | 2010 FBC / 2008 NEC | | | | | | DENIED BY ELECTRICAL | | | | | | EXISTING STORAGE AREA THAT IS BEING CONVERTED TO LIVING | | | SPACE SHALL COMPLY WITH THE FOLLOWING: | | | | | | 1) PROVIDE LOAD CALCULATIONS AND A PANEL SCHEDULE FOR | | | THE EXISTING 60 AMP PANEL. CITY AMENDMENTS 107.2.1 AND | | | NEC 220.40 | | | | | | 2) COMPLY WITH NEC 210.52 (A) FOR RECEPTACLE OUTLET | | | SPACING. | | | | | | 3) COMPLY WITH NEC 210.70 FOR REQUIRED LIGHTING | | | OUTLETS. | | | | | | 4) SHOW COMPLIANCE WITH FBC 210.12 FOR ARC-FAULT | | | CIRCUIT-INTERRUPTER PROTECTION (AFCI). | | | | | | 5) SHOW COMPLIANCE WITH FBC 406.11 FOR TAMPER-RESISTANT | | | RECEPTACLES. | | | | | | 6) SHOW COMPLIANCE WITH FBCR 314.3.1 FOR SMOKE ALARMS. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|