| 2014-07-18 16:41:17 | 2010 FBC |
| | |
| | DENIED BY BUILDING |
| | |
| | 1) ON THE LATEST PLAN SUBMITTAL THE STORAGE SHED |
| | EXTENSION IS NOW BEING CALLED A CABANA WITH A BATH. A |
| | CABANA IS CONSIDERED LIVING SPACE AND WILL NEED AN |
| | IMPACT FEE REVIEW AND A CERTIFICATE OF OCCUPANCY IS |
| | REQUIRED BEFORE THE BUILDING CAN BE OCCUPIED. FBC |
| | EXISTING BUILDING 901.4 |
| | |
| | 2) THIS IS A CHANGE OF OCCUPANCY FROM A UTILITY TO AN |
| | R-3. THIS IS A CHANGE TO A HIGHER HAZARD CATEGORY PER |
| | THE FBC EXISTING BUILDING SECTION 912.3. THE EXISTING |
| | STRUCTURE IS REQUIRED TO BE ANALYZED AND IS REQUIRED TO |
| | COMPLY WITH THE WINDLOAD REQUIREMENTS FOR A RISK |
| | CATEGORY II STRUCTURE. FBC EXISTING BUILDING 907.2 |
| | |
| | 3) THE ROOM WITH THE CLOSET IS CONSIDERED A BEDROOM |
| | (SLEEPING ROOM) AND IS REQUIRED TO HAVE A WINDOW THAT |
| | COMPLIES WITH FBC EXISTING BUILDING 912.4.1 (EXCEPTION |
| | 7) AND HAVE A CLEAR OPENING AREA OF NO LESS THAN 4 |
| | SQUARE FEET WITH MINIMUM OPENING HEIGHT OF 22 INCHES |
| | AND MINIMUM OPENING WIDTH OF 20 INCHES AND A MAXIMUM |
| | SILL HEIGHT OF 44 INCHES. |
| | |
| | 4) SMOKE ALARMS IN ACCORDANCE WITH FBCR 314 WILL BE |
| | REQUIRED. THERE IS ALSO ADDITIONAL ELECTRICAL |
| | REQUIREMENTS FOR A RESIDENTIAL OCCPANCY. |
| | |
| | 5) FBC 306.4 FOR REQUIRED HOT AND COLD WATER FOR THE |
| | BATHROOM. |
| | |
| | 6) SHOW COMPLIANCE WITH FBC ENERGY CONSERVATION |
| | SECTIONS 101.4.1 AND 103.2. |
| | |
| | 7) SUBMIT TWO COPIES OF THE PRODUCT APPROVALS FOR THE |
| | WINDOWS AS REQUIRED BY DCA RULE 9N-3. |
| | |
| | 8) SUBMIT TWO COPIES OF AN INSTALLATION SCHEDULE AND A |
| | KEY PLAN FOR THE STORM PANELS. SPECIFY THE ANCHOR TYPE, |
| | CONNECTION TYPE AND ANCHOR SPACING. SEE THE ANCHOR |
| | SCHEDULES ON SHEET 3 OF THE PRODUCT APPROVAL. CITY |
| | AMENDMENTS 107.2.1 AND 301.1 |
| | |
| | 9) THE PLANS SHOW 2 X 4 CEILING JOISTS SPANNING OVER 11 |
| | FEET, WHICH EXCEEDS THE SPANS ALLOWED BY THE AF & PA |
| | TABLES. PLEASE CORRECT. FBC R801.2 |
| | |
| | 10) THE VALUE OF WORK ON THE PERMIT APPLICATION IS |
| | $3900.00. THIS IS TOO LOW FOR THE WORK THAT IS |
| | SPECIFIED . FOR PERMIT VALUATION PURPOSES THE VALUE IS |
| | THE TOTAL REPLACEMENT VALUE. PLEASE SUBMIT A COST |
| | BREAKDOWN INCLUDING LABOR, MATERIALS, DESIGN COSTS AND |
| | OVERHEAD AND PROFIT AS WOULD BE CHARGED BY A |
| | CONTRACTOR. CITY AMENDMENT 109.3 |
| | |
| | 11) PLEASE SUBMIT A RESPONSE LETTER INDICATING HOW EACH |
| | OF THE REVIEW ITEMS HAS BEEN ADDRESSED. |
| | |
| | ROBERT MCDOUGAL |
| | BLDG. PLAN REVIEW |
| | (561)805-6714 |
| | [email protected] |
| | |
| | |
| | |
| | ***********************************THIS REVIEW IS NOT |
| | COMPLETE AT THIS TIME. |
| | *************************************** |
| | |
| | |
| | |