| 2014-06-19 19:01:21 | 2010 FBC |
| | |
| | DENIED BY BUILDING |
| | |
| | 1) THE NAME AND SIGNATURE OF THE PERSON RESPONSIBLE FOR |
| | THE DESIGN IS REQUIRED ON THE PLANS. CITY AMENDMENTS |
| | 107.2.1 |
| | |
| | 2) SUBMIT TO COPIES OF A SURVEY THAT SHOWS THE LOCATION |
| | OF THE EXISTING STORAGE BUILDING AND THE ADDITION AND |
| | THE DISTANCE TO PROPERTY LINES AND OTHER BUILDINGS ON |
| | THE SAME PROPERTY. FBC R302.1 |
| | |
| | 3) THE MEAN ROOF HEIGHT ON THE COVER SHEET IS LISTED AS |
| | 30 FEET AND IT IS SPECIFIED AS 15 FEET ON SHEET 8. |
| | PLEASE CORRECT. CITY AMENDMENT 107.2.1 |
| | |
| | 4) ON SHEET 5.0 THE FOOTING IS SPECIFIED AS 8" X 12" |
| | WITH 6" ABOVE GRADE AND 6" BELOW GRADE. FBCR 403.1 |
| | REQUIRES FOOTINGS TO BE A MINIMUM OF 12" WIDE AND FBCR |
| | 403.1.4 REQUIRES THE BOTTOM OF FOOTINGS TO BE A MINIMUM |
| | OF 12" BELOW GRADE. PLEASE CORRECT. |
| | |
| | 5) ON SHEET 6.0 THE RAFTER SPACING IS 1' 4" ON THE |
| | FRAMING PLAN AND 24" O.C. ON THE TYPICAL END DETAIL |
| | NOTE. PLEASE CORRECT. CITY AMENDMENT 107.2.1 |
| | |
| | 6) THE VALUE OF WORK ON THE PERMIT APPLICATION IS |
| | $3900.00. THIS APPEARS TO BE LOW FOR A BATHROOM |
| | ADDITION. FOR PERMIT VALUATION PURPOSES THE VALUE IS |
| | THE TOTAL REPLACEMENT VALUE. PLEASE SUBMIT A COST |
| | BREAKDOWN INCLUDING LABOR, MATERIALS, DESIGN COSTS AND |
| | OVERHEAD AND PROFIT AS WOULD BE CHARGED BY A |
| | CONTRACTOR. CITY AMENDMENT 109.3 |
| | |
| | 7) SPECIFY THE CONNECTORS THAT WILL BE USED TO ATTACH |
| | THE OUTLOOKERS AT THE GABLE END. FBC R301.1 & R802.1.9 |
| | |
| | 8) SPECIFY THE CONNECTORS OR ANCHORS THAT WILL BE USED |
| | TO ATTACH THE WALLS TO THE SLAB. FBC R301.1 |
| | |
| | 9) SUBMIT TWO COPIES OF THE PRODUCT APPROVALS FOR THE |
| | EXTERIOR DOOR AND WINDOWS, THE SIMPSON CONNECTORS ( |
| | MTS12, H2.5 AND A23) AS REQUIRED BY DCA RULE 9N-3. |
| | |
| | 10) SUBMIT TWO COPIES OF A KEY PLAN AND INSTALLATION |
| | SCHEDULE FOR THE STORM PANELS. CITY AMENDMENT 107.2.1 |
| | AND FBCR 301.1 |
| | |
| | 11) THE PLANS SHOW 2 X 4 CEILING JOISTS SPANNING OVER |
| | 11 FEET, WHICH EXCEEDS THE SPANS ALLOWED BY THE AF & PA |
| | TABLES. PLEASE CORRECT. FBC R801.2 |
| | |
| | 12) PLEASE SUBMIT A RESPONSE LETTER INDICATING HOW EACH |
| | OF THE REVIEW ITEMS HAS BEEN ADDRESSED. |
| | |