2014-11-05 16:32:44****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2010
 FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL
  
 1. ALL OPENINGS HAVE HORIZONTAL INSTALLATION PROPOSED
 WITH CONCRETE SUBSTRATE. FILLED CELLS ARE MASONRY, NOT
 CONCRETE.
  
 2. THE SHUTTER CONNECTION MOUNTING TYPE SHOULD
 CORRELATE WITH THE ANCHOR CHARTS ON SHEETS 5 - 7. FOR
 EXAMPLE, 1 (TOP), 2 (BOTTOM), ETC. PLEASE REVISE.
 PLEASE NOTE THAT THE FASTENER PROPOSED CANNOT BE USED
 FOR MANY OF THE MOUNTING TYPES (HAS "NA" IN THE BOX).
  
 3. FROM PREVIOUS LIST - SHOW THE EMERGENCY MEANS OF
 ESCAPE, FBC R310.4. INCLUDE THE ROOM DESIGNATION.
  
 4. FROM PREVIOUS LIST - PROVIDE A FLOOR PLAN SHOWING
 WHERE THE SHUTTERS WILL BE INSTALLED AND PANEL SIZES
 WHICH CORRELATES WITH THE INSTALLATION SCHEDULE, ITEM 1
 ABOVE. FBC R301, FBC1609, FBC*106.
  
 THIS CAN BE DONE USING THE FLOOR PLAN ALREADY PROVIDED.
 LABEL THE PROPOSED PANELS IN ACCORDANCE WITH THE FLOOR
 PLAN. OR, YOU CAN PROVIDE A NEW FLOOR PLAN.
  
  