2014-07-09 08:50:19RESIDENTIAL (R3) ADDITION/ALTERATION MECHANICAL REVIEW
 SECOND CHECKLIST.
 CODE: 2010 FBC.
  
 1- EQUIPMENT SIZING CALCULATIONS SUBMITTED:
 EQUIPMENT SIZING CALCULATIONS TO INCLUDE THE
 MANUFACTURER AND MODEL NUMBER OF THE OUTDOOR AND INDOOR
 UNITS ALONG WITH THE SENSIBLE AND TOTAL COOLING
 CAPACITIES AS REQUIRED BY SEC. 403.6 OF 2010 FBC-ENERGY
 CONSERVATION (REPEAT COMMENT).
  
 2- A/C PLAN:
 A) SIZE OF RETURN AIR TRANSFER DUCT IN THE MASTER
 BEDROOM DOESN'T COMPLY WITH EXCEPTION #1 OF SEC.
 M1602.4 OF 2010 FBC-RESIDENTIAL. THE SIZE OF THE
 TRANSFER DUCT NEED TO BE INCREASED TO 14" MIN. NOTE:
 ALL THE SUPPLY AIR INTO THE MASTER BEDROOM SHALL BE
 INCLUDED WHEN SIZING THE DUCT.
  
 B) PROVIDE NAME, SIGNATURE AND LICENSE NUMBER OF THE
 A/C CONTRACTOR DOING THE WORK AS REQUIRED BY FLORIDA
 STATUTE 471.003 AND SEC. 107.2.1 CITY AMENDMENTS TO
 FBC.
  
 C) PROVIDE AL THE EQUIPMENT INFORMATION (MANUFACTURER,
 MODEL ETC). . AND LOCATION INCLUDING THE CONDENSER
 UNIT. SEC. 107.3.5.3 CITY AMENDMENTS
  
 ***PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO EXPEDITE THE REVIEW PROCESS.
  