| Plan Review Notes For Permit 14050584 |
| Permit Number |
14050584 |
|
| Review Stop |
FIRE |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2014-06-11 11:19:47 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | HAVING REVIEWED THE SITE PLAN FOR THE FIRST TIME, THERE | | | ARE MULTIPLE TEMPORAY TRAILERS INDICATED IN THE PARKING | | | LOT AREA. | | | | | | THESE TEMPORAY TRAILERS SHALL MEET THE MINIMUM | | | SEPARATION DISTANCE REQUIREMENTS OF NFPA 241, CHAPTER | | | 4, TABLE 4.2.1. | | | | | | SEPARATION DISTANCES SHALL BE PROVIDED ON THE SITE | | | PLAN. THE TRAILERS SHALL BE SEPARATED ACCORDING TO THE | | | INDICATED SEPARATION DISTANCES. | | | | | | A 75 PERCENT REDUCTION IN SEPARATION DISTANCE SHALL BE | | | APPLIED PROVIDED AUTOMATIC SPRINKLER PROTECTION IS USED | | | IN THE EXPOSING STRUCTURE. | | | | | | AS PROPOSED, FIRE SPRINKLER PROTECTION IS REQUIRED IN | | | EACH OF THE TRAILERS ON THE SITE PLAN, SPRINKLER | | | PROTECTION SHALL BE INDICATED ON THE RESUBMITTED PLAN | | | UNDER SEPARATE SHOP DRAWINGS. | | | | | | ADA COMPLAINT STAIR/RAMP PLANS DO NOT SHOW LOCATIONS AT | | | THE THE BUILDING, TO OTHER TRAILERS AND/OR ON THE SITE | | | PLAN. |
|