| Notes |
| Date |
Text |
| 2014-09-15 15:06:54 | BUILDING PLAN REVIEW | | | PERMIT: 14050575 | | | ADD: 951 HANK AARON DR | | | CONT: CORPORATE PROPERTY SERVICES, INC | | | TEL: (954) 426-5144 | | | | | | 2010 FLORIDA BUILDING CODE W | | | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA | | | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION | | | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. | | | | | | 2010 EXISTING BUILDING CODE LEVEL II 701.3 | | | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, | | | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS | | | OF THE FLORIDA BUILDING CODE, BUILDING. | | | | | | 3RD REVIEW | | | DATE: MOJN. SEPT. 15/ 2014 | | | ACTION: BUILDING PROVISO | | | | | | 1) ROOFING PRODUCT APPROVAL SUBMITTED FL 16039-R3 | | | DURO-LAST ROOFING INC. PAGE 39OF 40 OPTION W-M-6 GOOD | | | FOR -60 PSF AND LIMITATION #7 FOR ZONES 2 & 3 WILL | | | REQUIRE ENHANCED FASTENING, RAS 117 CALCULATIONS. IF | | | THE CALCULATIONS ARE NOT COMPLETED BY THE DESIGNER OF | | | RECORD, THEN THEY WILL NEED TO BE REVIEWED BY THE | | | DESIGNER OF RECORD BEFORE SUBMITTAL TO THE BUILDING | | | DEPARTMENT. | | | | | | 2010 FBC-B 1609.1.1 DETERMINATION OF WIND DESIGN- | | | CHAPTER 6 OF ASCE- 7-10. | | | | | | JAMES A. WITMER CBO | | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | | TEL: 561-805-6715 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | | | | | | | |
|