| 2014-08-01 12:15:19 | DATE: 8/1/2014 |
| | PROJECT: WEDNDY'S RENNOVATION |
| | PERMIT#: 14050575 |
| | CODE: 2008 EDITION OF THE NEC |
| | 2010 EDITION OF THE FBC |
| | 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, |
| | ADMINISTRATION, 2012 FBC SUPPLEMENTS. |
| | |
| | 2ND ELECTRICAL PLAN REVIEW |
| | ACTION: DENIED |
| | |
| | 1) INDICATE THE LOCATION OF THE ELECTRICAL SERVICE AND |
| | HOW THE UNFUSED SERVICE ENTRANCE CONDUCTORS ARE ROUTED |
| | TO PANEL MDP. |
| | |
| | 2) REVISE ONE LINE RISER DIAGRAM TO INDICATE ALL FEEDER |
| | SIZES, AND PANEL SCHEDULES FOR SERVICE ENTRANCE THROUGH |
| | PANELS "MDP", "A" AND "B" |
| | |
| | 3) PROVIDE GROUNDING ELECTRODE SYSTEM DETAIL TO |
| | INDICATE WIRE SIZES, MAIN BONDING JUMPER, AND ALL |
| | AVAILABLE GROUNDING ELECTTRODE TYPES, SIZES AND |
| | LOCATIONS. |
| | |
| | SEPARATE PERMITS ACCOMPANIED BY SHOP DRAWINGS REQUIRED |
| | FOR SIGNS, SECURITY, NETWORK, CCTV, AUDIO/VIDEO AND FOR |
| | THE INSTALLATION AND TERMINATION OF THE OUTDOOR MENU |
| | BOARDS, CANOPY, AND PRE-SALE BOARD. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. SEE LINK: HTTP://WPB.ORG/DEVELOPMENT |
| | /WP-CONTENT/UPLOADS/SITES/33/2013/09/APPLICATION_RESUBM |
| | ITTAL_FORM_04132010.PDF |
| | |
| | ADDITIONALLY, PLEASE INSERT CORRECTED PAGES INTO |
| | SUBMITTAL PACKAGE AND LEAVE THE PREVIOUSLY REVIEWED |
| | SHEETS FOR COMPARATIVE REVIEW. |
| | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, |
| | 561-805-6717 OR [email protected] |
| | |