| 2014-06-04 10:13:55 | ADDRESS: 951 HANK AARON DR. WPB |
| | PERMIT#:14050575 |
| | 1ST ELECTRICAL REVIEW |
| | ACTION: DENIED. |
| | CODE: 2008 NEC AND 2010 FBC |
| | |
| | DEFICIENCIES: |
| | 1) THE ELECTRICAL SERVICE LOAD SUMMARY SUBMITTED IS |
| | BASED ON AN EXISTING ELECTRICAL LOAD PER NEC 220.87. |
| | |
| | THIS NEC CODE ARTICLE QUOTED ON THE SUBMITTAL NEC |
| | 220.87 STATES IN PART: |
| | THE CALCULATION OF A FEEDER OR SERVICE LOAD FOR |
| | EXISTING INSTALLATIONS SHALL BE PERMITTED TO USE |
| | "ACTUAL MAXIMUM DEMAND" TO DETERMINE THE EXISTING LOAD |
| | UNDER ALL OF THE FOLLOWING CONDITIONS: |
| | 1) THE MAXIMUM DEMAND DATA IS AVAILABLE FOR A ONE YEAR |
| | PERIOD. |
| | 2) THE MAXIMUM DEMAND AT 125% PLUS THE NEW LOAD DOES |
| | NOT EXCEED THE AMPACITY OF THE FEEDER OR RATING OF THE |
| | SERVICE. |
| | 3) THE FEEDER HAS OVERCURRENT PROTECTION IN ACCORDANCE |
| | WITH 240.4 AND THE SERVICE HAS OVERLOAD PROTECTION IN |
| | ACCORDANCE WITH 230.90. |
| | |
| | THE PROBLEM IS WHAT HAS BEEN SUBMITTED IS AN "ASSUMED |
| | MAXIMUM DEMAND" WITH NO EVIDENCE OF THE "ACTUAL MAXIMUM |
| | DEMAND" BEING SUBMITTED AT ALL. |
| | |
| | PLEASE COMPLY COMPLETELY WITH THE ARTICLE AS STATED OR |
| | SUBMIT A COMPLETE ELECTRICAL LOAD SUMMARY SHOWING |
| | COMPLIANCE WITH PART III OF ARTICLE 220, MORE |
| | SPECIFICALLY ARTICLE 220.40 WHICH STATES: |
| | |
| | THE CALCULATED LOAD OF A FEEDER OR SERVICE SHALL NOT BE |
| | LESS THAN THE SUM OF THE LOADS ON THE BRANCH CIRCUITS |
| | SUPPLIED AS DETERMINED BY PART II OF ARTICLE 220, AFTER |
| | ANY APPLICABLE DEMAND FACTORS PERMITTED BY PART III OR |
| | IV OR REQUIRED BY PART V HAVE BEEN APPLIED. |
| | |
| | 2) PROVIDE SAFETY LABELING FOR FLASH PROTECTION AND FOR |
| | THE PANEL BOARDS AND MAIN DISCONNECTING MEANS. NEC |
| | 110.22, 110.16, 110.22 |
| | |
| | 3) THE BRANCH CIRCUIT FEEDING BATTERY BACKED EMERGENCY |
| | AND EXIT LIGHTS SHALL BE THE SAME BRANCH CIRCUIT AS |
| | THAT SERVING THE NORMAL LIGHTING IN THE AREA AND |
| | CONNECTED AHEAD OF ANY LOCAL SWITCHES. NEC 701.11(G) |
| | |
| | 4) LIGHTING FOR ALL EXTERIOR APPLICATIONS NOT EXEMPTED |
| | IN SECTION 505.1 SHALL HAVE AUTOMATIC CONTROLS CAPABLE |
| | OF TURNING OFF EXTERIOR LIGHTING WHEN SUFFICIENT |
| | DAYLIGHT IS AVAILABLE OR WHEN THE LIGHTING IS NOT |
| | REQUIRED DURING NIGHTTIME HOURS. LIGHTING NOT |
| | DESIGNATED FOR DUSK-TO-DAWN OPERATION SHALL BE |
| | CONTROLLED BY AN ASTRONOMICAL TIME SWITCH OR |
| | PHOTOSENSOR. ALL TIME SWITCHES SHALL BE CAPABLE OF |
| | RETAINING PROGRAMMING AND THE TIME SETTING DURING LOSS |
| | OF POWER FOR A PERIOD OF AT LEAST 10 HOURS. |
| | |
| | 5) ALL COMPONENTS AND CABLES SHALL BE UL LISTED AND |
| | LABELED FOR USE IN THE MANNER INSTALLED. NEC 110.3 |
| | |
| | SEPARATE SHOP DRAWINGS AND PERMITS REQUIRED FOR SIGNS, |
| | SECURITY, NETWORK, CCTV, AUDIO/VIDEO AND FOR THE |
| | INSTALLATION AND TERMINATION OF THE OUTDOOR MENU |
| | BOARDS, CANOPY, AND PRE-SALE BOARD. |
| | |
| | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421. |
| | 561-805-6717 OR [email protected] |
| | |