| 2014-06-13 11:27:25 | BUILDING PLAN REVIEW |
| | PERMIT: 14050575 |
| | ADD: 951 HANK AARON DR |
| | CONT: CORPORATE PROPERTY SERVICES, INC |
| | TEL: (954) 426-5144 |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: FRI. JUNE 13/ 2014 |
| | ACTION: DENIED |
| | |
| | 1) SHEET A5 ENLARGED RESTROOM PLANS INDICATE IN BOTH |
| | THE MENS & WOMENS TOLIET COMPARTMENTS WITHIN THE |
| | RESTROOM SWING INTO THE REQUIRED FIXTURE AREA. PLEASE |
| | SEE THE 2010 FBC-ACCESSIBILITY CODE 604.8.1.2. THESE |
| | ARE TOLIET COMPARTMENTS NOT SINGLE USER TOLIET ROOMS |
| | WHICH ARE COVERED UNDER |
| | 603.2.3 EXCEPTION # 2, TOILET ROOMS FOR INDIVIDUAL USE. |
| | |
| | 2) THE SUBMITTED PRODUCT APPROVALS HAVE NOT BEEN |
| | REVIEWED BY THE DESIGNER OF RECORD. 2010 FBC 107.3.4.1 |
| | PRODUCT APPROVALS. THOSE PRODUCTS WHICH ARE REGULATED |
| | BY THE DCA RULE 9N-03 SHALL BE REVIEWED AND APPROVED IN |
| | WRITING BY THE DESIGNER OF RECORD PRIOR TO SUBMITTAL |
| | FOR JURISDICTIONAL APPROVAL. |
| | FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR |
| | SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, |
| | SHOP DRAWINGS ETC.. |
| | |
| | 3) SUBMITTED NOA 12-1003.06 STYLE RIB METAL WALL PANEL |
| | WAS NOT SUBMITTED WITH THE TECHNICAL SHEETS/ |
| | INSTALATION SHEET. 107.2.1.3 ADDITIONAL INFORMATION IS |
| | REQUIRED. |
| | |
| | 4) THE ROOFING APPROVAL FL 16039-R3 WAS SUBMITTED, NO |
| | SUB-SYSTEM NOR PRESSURES WERE IDENTIFIED. 2010 WEST |
| | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| | CHAPTER 1, 107.2.1.2 FOR ROOF ASSEMBLIES REQUIRED BY |
| | THE CODE, THE CONSTRUCTION DOCUMENTS SHALL ILLUSTRATE, |
| | DESCRIBE AND DELINEATE THE TYPE OF ROOFING SYSTEM, |
| | MATERIALS, FASTENING REQUIREMENTS, FLASHING |
| | REQUIREMENTS AND WIND RESISTANCE RATING THAT ARE |
| | REQUIRED TO BE |
| | INSTALLED. PRODUCT EVALUATION AND INSTALLATION SHALL |
| | INDICATE COMPLIANCE WITH THE WIND CRITERIA REQUIRED FOR |
| | THE SPECIFIC SITE OR A STATEMENT BY AN ARCHITECT OR |
| | ENGINEER FOR THE SPECIFIC SITE MUST BE SUBMITTED WITH |
| | THE CONSTRUCTION DOCUMENTS |
| | |
| | 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS |
| | WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE |
| | REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF |
| | RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| | FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR |
| | SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, |
| | SHOP DRAWINGS ETC.. |
| | |