Plan Review Notes
Plan Review Notes For Permit 14050575
Permit Number 14050575
Review Stop B
Sequence Number 1
Notes
Date Text
2014-06-13 11:27:25BUILDING PLAN REVIEW
 PERMIT: 14050575
 ADD: 951 HANK AARON DR
 CONT: CORPORATE PROPERTY SERVICES, INC
 TEL: (954) 426-5144
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: FRI. JUNE 13/ 2014
 ACTION: DENIED
  
 1) SHEET A5 ENLARGED RESTROOM PLANS INDICATE IN BOTH
 THE MENS & WOMENS TOLIET COMPARTMENTS WITHIN THE
 RESTROOM SWING INTO THE REQUIRED FIXTURE AREA. PLEASE
 SEE THE 2010 FBC-ACCESSIBILITY CODE 604.8.1.2. THESE
 ARE TOLIET COMPARTMENTS NOT SINGLE USER TOLIET ROOMS
 WHICH ARE COVERED UNDER
 603.2.3 EXCEPTION # 2, TOILET ROOMS FOR INDIVIDUAL USE.
  
 2) THE SUBMITTED PRODUCT APPROVALS HAVE NOT BEEN
 REVIEWED BY THE DESIGNER OF RECORD. 2010 FBC 107.3.4.1
 PRODUCT APPROVALS. THOSE PRODUCTS WHICH ARE REGULATED
 BY THE DCA RULE 9N-03 SHALL BE REVIEWED AND APPROVED IN
 WRITING BY THE DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 3) SUBMITTED NOA 12-1003.06 STYLE RIB METAL WALL PANEL
 WAS NOT SUBMITTED WITH THE TECHNICAL SHEETS/
 INSTALATION SHEET. 107.2.1.3 ADDITIONAL INFORMATION IS
 REQUIRED.
  
 4) THE ROOFING APPROVAL FL 16039-R3 WAS SUBMITTED, NO
 SUB-SYSTEM NOR PRESSURES WERE IDENTIFIED. 2010 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1, 107.2.1.2 FOR ROOF ASSEMBLIES REQUIRED BY
 THE CODE, THE CONSTRUCTION DOCUMENTS SHALL ILLUSTRATE,
 DESCRIBE AND DELINEATE THE TYPE OF ROOFING SYSTEM,
 MATERIALS, FASTENING REQUIREMENTS, FLASHING
 REQUIREMENTS AND WIND RESISTANCE RATING THAT ARE
 REQUIRED TO BE
 INSTALLED. PRODUCT EVALUATION AND INSTALLATION SHALL
 INDICATE COMPLIANCE WITH THE WIND CRITERIA REQUIRED FOR
 THE SPECIFIC SITE OR A STATEMENT BY AN ARCHITECT OR
 ENGINEER FOR THE SPECIFIC SITE MUST BE SUBMITTED WITH
 THE CONSTRUCTION DOCUMENTS
  
 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  