| Date |
Text |
| 2014-06-19 15:51:48 | 2010 FBC |
| | |
| | DENIED BY BUILDING |
| | |
| | 1) SUBMIT TWO COPIES OF A SURVEY FOR EACH UNIT TO SHOW |
| | THAT THE PROPERTY HAS BEEN SUB-DIVIDED TO CREATE |
| | TOWNHOUSES. |
| | |
| | 2) EACH OF THE NEW TOWNHOUSES ARE REQUIRED TO HAVE |
| | THEIR OWN STREET ADDRESS. CONTACT SCOTT ALEF AT |
| | 561-494-1094. |
| | |
| | 3) ONE OF THE APPROVED PLANS WILL HAVE TO BE REVIEWED |
| | BY PALM BEACH COUNTY TO DETERMINE IF ANY IMPACT FEES |
| | ARE DUE. |
| | |
| | 4) THE ENERGY CALCULATIONS AND EQUIPMENT SIZING |
| | CALCULATIONS CAN NOT BE WORSE CASE. THEY ARE REQUIRED |
| | TO BE SITE SPECIFIC. EACH TOWNHOUSE IS REQUIRED TO HAVE |
| | ENERGY CALCULATIONS AND EQUIPMENT SIZING CALCULATIONS. |
| | THE ADDRESS OF EACH UNIT IS REQUIRED ON THE FORM AND |
| | THE UNIT TYPE (IE. GARAGE RIGHT, GARAGE LEFT, INTERIOR |
| | UNIT, END UNIT, ETC.). FBC ENERGY CONSERVATION 401.2 |
| | |
| | 5) CORRECT THE WIND DESIGN DATA ON SHEET T-2. THE |
| | CORRECT WINDSPEED FOR THIS PROJECT IS 170 MPH VULT / |
| | 132 VASD. FBCR 301.2.1 |
| | |
| | 6) PROVIDE ADDITIONAL DETAILS FOR THE STEEL BUCKET |
| | TRUSS HANGER IN THE CONNECTOR SCHEDULE ON SHEET T-2. |
| | PROVIDE A SIDE VIEW WITH DIMENSIONS AND SPECIFY THE |
| | WELD TYPES. CITY AMENDMENTS 107.2.1.3 |
| | |
| | 7) THE ROOF SLOPE IS SPECIFIED AS 5/12 ON SHEET 3 AND |
| | ON SHEET T-2 AND THE TYPICAL END DETAIL IT IS 4/12. |
| | PLEASE CORRECT. CITY AMENDMENTS 107.2.1 |
| | |
| | 8) ON SHEET D1 THE FLOOR TRUSS BEARING LEDGER IS |
| | SPECIFIED AS (2) 2 X 6S AND ON SHEETS W-1 & T-1 IT IS |
| | (2) 2 X 12S. PLEASE CORRECT. CITY AMENDMENTS 107.2.1 |
| | |
| | 9) THE ANCHORS THAT ARE SPECIFIED FOR THE LEDGER ARE |
| | INCONSISTENT. 1/2", 5/8" & 3/4" DIAMETERS AND 4-1/2" & |
| | 5" EMBED DEPTHS ARE GIVEN. PLEASE CORRECT. CITY |
| | AMENDMENTS 107.2.1 |
| | |
| | 10) SHOW COMPLIANCE WITH FBCR 302.6 FOR DWELLING / |
| | GARAGE FIRE SEPARATION REQUIREMENTS FOR MINIMUM 5/8" |
| | TYPE X DRYWALL ON CEILING. |
| | |
| | 11) SHOW COMPLIANCE WITH FBCR 302.5.1 AND FBC ENERGY |
| | CONSERVATION FOR REQUIREMENTS FOR THE DOOR FROM THE |
| | GARAGE TO THE RESIDENCE. |
| | |
| | 12) THE PRODUCT APPROVALS ARE REQUIRED TO BE REVIEWED |
| | AND APPROVED IN WRITING BY THE DESIGNER OF RECORD FOR |
| | THE PROJECT. CITY AMENDMENTS 107.3.4.1 |
| | |
| | 13) SUBMIT PRODUCT APPROVALS FOR THE IMPACT RATED |
| | WINDOWS AND DOORS, STRUCTURAL MULLIONS, SLIDING GLASS |
| | DOOR, OVERHEAD GARAGE DOOR, ROOF MATERIALS FOR THE FLAT |
| | ROOF AS REQUIRED BY DCA RULE 9N-3. |
| | |
| | ROBERT MCDOUGAL |
| | BLDG. PLAN REVIEW |
| | (561)805-6714 |
| | [email protected] |