| 2014-05-20 19:16:42 | PERMITS 14050547, 14050556, 14050561, 14050566 |
| | THE ABOVE MENTIONED PERMITS WERE REVIEWED FOR |
| | ELECTRICAL COMPLIANCE TODAY. AS A RESULT OF THE REVIEW, |
| | THE FOLLOWING COMMENTS WERE GENERATED. SOME ARE UNIT |
| | SPECIFIC AND OTHERS PERTAIN TO THE PROJECT AS A WHOLE. |
| | 1. YOU SHALL PROVIDE A SITE PLAN INDICATING THE |
| | LOCATION OF THE FPL SOURCE OF POWER TO EACH OF THE |
| | UNITS. IF ANY OF THE FPL FEEDERS INTERSECT OR CROSS |
| | UNDER AN ADJOINING LOT, PROVISIONS FOR A RECORDED |
| | EASEMENT SHALL BE ADDRESSED. |
| | 2. THE SUBMITTED ELECTRICAL PLANS DO NOT INDICATE THE |
| | LOCATION OF THE ELECTRIC METER FOR UNITS 2 & 3. THERE |
| | SHALL BE A SERVICE DISCONNECT IN ACCORDANCE WITH NEC |
| | 230.70(A)(1). |
| | 3. IN ADDITION TO THE ELECTRICAL NOTES ALREADY ON THE |
| | PLANS, A NOTE AS TO THE CEILING BOX REQUIREMENT OF NEC |
| | 314.27 SHALL BE MADE. |
| | 4. AS A SUGGESTION, A 3 WAY SWITCH SHOULD BE ADDED IN |
| | THE LIVING ROOM BETWEEN THE ENTRY WAY AND THE STAIRS. |
| | 5. BECAUSE THE SUBMITTED PANEL SCHEDULES PROVE TO BE |
| | GENERIC AS WELL AS THE LOAD CALCS, I WENT OVER THEM AND |
| | THE SERVICE CONDUCTORS AS INDICATED ON THE RISER |
| | DIAGRAMS ARE ADEQUATE FOR THE LOAD. |
| | I. IN ADDITION TO THE ABOVE MENTIONED, THE ONLY OTHER |
| | CORRECTIONS REQUIRED WOULD BE TO BETTER SCRUTINIZE THE |
| | LINEAR WALL SPACE FOR COMPLIANCE WITH THE VARIOUS |
| | REQUIREMENTS OF NEC 210.52. |
| | I HAVE GREEN LINED ONE OF THE SETS WITH THE OUTLET |
| | PLACEMENT FOR CODE COMPLIANCE. FEEL FREE TO COME IN TO |
| | CHECK OUT THIS SET FOR YOUR CORRECTIONS. |
| | THESE PLANS WERE REVIEWED BY MIKE ALBARRAN, ELECTRICAL |
| | PLANS EXAMINER |
| | YOU ARE WELCOME TO REVIEW STATUS OR COMMENTS AT THE |
| | FOLLOWING LINK: |
| | |
| | HTTP://ONESTOPSHOP.WPBGOV.COM/EGOVPLUS/PERMIT/PERM_STAT |
| | US.ASPX |
| | |
| | ENTER YOUR PERMIT NUMBER (SEE SUBJECT LINE OF THIS |
| | EMAIL FOR YOUR PERMIT #), CLICK ON THE PERMIT NUMBER, |
| | AND THEN GO TO "PLAN REVIEWS" TO SEE YOUR COMMENTS (TAB |
| | ABOVE THE SECOND PERMIT INFORMATION). |
| | AFTER ISSUANCE, PLEASE CHECK YOUR PLAN CAREFULLY FOR |
| | COMPLIANCE WITH ANY NOTES, PROVISOS, OR OTHER PERMIT |
| | CONDITIONS. |
| | FOR FURTHER ASSISTANCE, PLEASE FEEL FREE TO CONTACT ME. |