| Plan Review Notes For Permit 14050545 |
| Permit Number |
14050545 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2014-05-15 13:00:17 | ELECTRICAL PROVISO: | | | | | | ELECTRCAL INSTALLATIONS IN HOLLOW SPACES, VERTICAL | | | SHAFTS, VENTILLATION OR AIR HANDLING DUCTS SHALL BE | | | MADE SO THAT THE POSSIBLE SPREAD OF FIRE OR PRODUCTS OF | | | COMBUSTION WILL NOT BE SUBSTANTIALLY INCREASED. | | | OPPENINGS AROUND ELECTRICAL PENETRATIONS THROUGH | | | FIRE-RESISTANT-RATED WALLS PENETRATIONS, FLOORS, OR | | | CEILINGS SHALL BE FIRESTOPPED USING APPROVED MEATHODS | | | TO MAINTAIN THE FIRE RESISTAVE RATING. PER THE 2008 | | | EDITION OF THE NEC ARTICLE 300.21 | | | | | | ANY AND ALL PENETRATIONS AT FIRE RATED PARTIONS SHALL | | | ALSO COMPLY WITH THE PROVISIONS OF THE 2010 FBC SECTION | | | 713 |
|