Plan Review Notes
Plan Review Notes For Permit 14050542
Permit Number 14050542
Review Stop P
Sequence Number 1
Notes
Date Text
2014-05-23 19:54:02PLUMBING PLAN REVIEW
 PERMIT: 14050542
 ADD: 801 S OLIVE AVE SUITE # 114 & 113
 CONT: ATLANTIC WINDOW CO.
 TEL: (561)248-4552
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: FRI. MAY 23/ 2014
 ACTION: DENIED
  
 1) THE NEW LOCATION OF THE KITCHEN SINK IS SHOWN TYING
 IN ON A POWDER ROOM WET VENT. THE WASTE TIE INTO THE
 WET VENT HAS TO HAPPEN PAST THE HORIZONTAL WET VENT
 BENEATH THE SLAB. 2010 FBC-P 909.2.1 HORIZONTAL WET
 VENT.
 THE DRY-VENT CONNECTION FOR A HORIZONTAL WET-VENT
 SYSTEM SHALL BE AN INDIVIDUAL VENT OR A COMMON VENT FOR
 ANY BATHROOM GROUP FIXTURE, EXCEPT AN EMERGENCY FLOOR
 DRAIN. WHERE THE DRY-VENT CONNECTS TO A WATER CLOSET
 FIXTURE DRAIN, THE DRAIN SHALL CONNECT HORIZONTALLY TO
 THE HORIZONTAL WET-VENT SYSTEM. NOT MORE THAN ONE
 WET-VENTED FIXTURE DRAIN SHALL DISCHARGE UPSTREAM OF
 THE DRY-VENTED FIXTURE DRAIN CONNECTION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]