Plan Review Notes
Plan Review Notes For Permit 14050542
Permit Number 14050542
Review Stop E
Sequence Number 1
Notes
Date Text
2014-05-21 12:07:52FIRST REVIEW FOR PERMIT 14050542
  
 THE ABOVE PERMIT CAME UP FOR ELECTRICAL REVIEW THIS
 MORNING AND THE FOLLOWING DEFICIENCIES WERE NOTED:
 1. THE DECLARED VALUATION NEEDS TO BE ADJUSTED AS PER
 THE W P B ADMINISTRATIVE: CODE 109.2 SCHEDULE OF PERMIT
 FEES. ON BUILDINGS, STRUCTURES, ELECTRICAL, GAS,
 MECHANICAL AND PLUMBING SYSTEMS OR ALTERATIONS
 REQUIRING A PERMIT, A FEE FOR EACH PERMIT SHALL BE PAID
 AS REQUIRED, IN ACCORDANCE WITH THE SCHEDULE
 ESTABLISHED BY THE APPLICABLE GOVERNING AUTHORITY.
 109.3* BUILDING PERMIT VALUATION.
 IF, IN THE OPINION OF THE BUILDING OFFICIAL, THE
 CLAIMED VALUATION OF BUILDING, ALTERATION, STRUCTURE,
 ELECTRICAL, GAS, MECHANICAL, OR PLUMBING SYSTEMS
 APPEARS TO BE UNDER ESTIMATED ON THE APPLICATION, THE
 PERMIT SHALL BE DENIED. FOR PERMITTING PURPOSES,
 VALUATION OF BUILDINGS AND SYSTEMS SHALL BE TOTAL
 REPLACEMENT PURPOSES, VALUATION OF BUILDINGS AND
 SYSTEMS SHALL BE THE TOTAL REPLACEMENT VALUE TO INCLUDE
 STRUCTURAL, ELECTRICAL, PLUMBING, MECHANICAL, INTERIOR
 FINISHES, NORMAL SITE WORK (EXCAVATION AND BACKFILL FOR
 BUILDINGS), ARCHITECTURAL AND DESIGN FEES, MARKETING
 COST, OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE.
 VALUATION REFERENCES MAY INCLUDE THE LATEST PUBLISHED
 DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES
 (MARSHALL-SWIFT, MEANS, ETC.) WITH REGIONAL ADJUSTMENTS
 FOR LOCATION AS PUBLISHED BY THE INTERNATIONAL CODE
 CONGRESS.
 2. THE ELECTRICAL NOTES REFER TO THE LATEST EDITION OF
 THE ELECTRICAL CODE. THOUGH THE 2011 EDITION IS OUT, IT
 HAS NOT BEEN ADOPTED AND THUS YOU SHALL COMPLY WITH THE
 2008 EDITION OF THE NEC.
 3. AS PER NEC 2008 SECTION 406.11, ALL NEW 125 VOLT, 15
 & 20 AMP RECEPTACLES IN DWELLING UNITS SHALL BE
 TAMPER-RESISTANT.
 4. AS PER NEC 210.8, ALL THE OUTLETS IN THE KITCHEN
 SHALL BE PROTECTED WITH GFCI.
 5. AS PER NEC 210.12, ALL NEW WIRING IN THE UNIT SHALL
 BE ARC-FAULT PROTECTED.
 6. FROM THE SUBMITTED DRAWING, IT IS NOT POSSIBLE TO
 DETERMINE IF A BACK SPLASH WILL BE USED AND/OR THE TYPE
 OF BACK SPLASH WHICH WILL BE USED. ALL NEW OUTLET BOXES
 IN THAT AREA SHALL COMPLY WITH THE DEPTH REQUIREMENTS
 OF NEC 314.21.
 7. OUTLET PLACEMENT REQUIREMENTS SHALL COMPLY WITH NEC
 210.52(B) & (C).
 8. SMOKE DETECTOR COMPLIANCE AS DICTATED IN FBC-R
 314.3.1 SHALL BE REQUIRED.
  
 THESE PLANS WERE REVIEWED BY MIKE ALBARRAN, ELECTRICAL
 PLANS EXAMINER
 YOU ARE WELCOME TO REVIEW STATUS OR COMMENTS AT THE
 FOLLOWING LINK:
  
 HTTP://ONESTOPSHOP.WPBGOV.COM/EGOVPLUS/PERMIT/PERM_STAT
 US.ASPX
  
 ENTER YOUR PERMIT NUMBER (SEE SUBJECT LINE OF THIS
 EMAIL FOR YOUR PERMIT #), CLICK ON THE PERMIT NUMBER,
 AND THEN GO TO "PLAN REVIEWS" TO SEE YOUR COMMENTS (TAB
 ABOVE THE SECOND PERMIT INFORMATION).
 AFTER ISSUANCE, PLEASE CHECK YOUR PLAN CAREFULLY FOR
 COMPLIANCE WITH ANY REDLINES, NOTES, PROVISOS, OR OTHER
 PERMIT CONDITIONS.
 FOR FURTHER ASSISTANCE, PLEASE FEEL FREE TO CONTACT ME.