Plan Review Notes
Plan Review Notes For Permit 14050542
Permit Number 14050542
Review Stop B
Sequence Number 1
Notes
Date Text
2014-05-23 19:03:11BUILDING PLAN REVIEW
 PERMIT: 14050542
 ADD: 801 S OLIVE AVE SUITE # 114 & 113
 CONT: ATLANTIC WINDOW CO.
 TEL: (561)248-4552
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: FRI. MAY 23/ 2014
 ACTION: DENIED
  
 1) PLEASE PROVIDE AFLOOR PLAN OF THE WHOLE UNIT, IT
 APPEARS A TENANT SEPERATION WALL IS BEING ELIMINATED
 JOINING TWO CONDOMINIUM UNITS TOGETHER. IF SO A UNITITY
 OF TITLE IS REQUIRED. UNITY OF TITLE. THE PROPOSED
 BUILDING STRUCTURE TRANSGRESSES LEGAL BOUNDARY LINES
 BETWEEN THE LOTS WHICH COMBINE TO FORM 'THE SITE'. A
 'UNITY OF TITLE' SHALL BE RECORDED AT THE COUNTY
 COURTHOUSE. SUBMIT A COPY OF THE RECORDED 'UNITY OF OF
 TITLE' DOCUMENT SO THAT FBC TABLE 601 BOUNDARY LINE
 REQUIREMENTS MAY BE DEEMED NOT APPLICABLE. SEE WEBSITE
 FOR APPLICATION:
 HTTP://WWW.WPB.ORG/ENGINEERING/ENG_FORMS.PHP
 "APPLICATION FOR UNITY OF TITLE"
 HTTP://WWW.WPB.ORG/ENGINEERING/UPLOADS/2010-10-12-14-45
 -38-UNITYOFTITLE3.PDF
  
 VINCENT J NOEL
 SURVEYOR/REAL ESTATE SUPERVISOR
 ENGINEERING SERVICES DEPARTMENT
 401 CLEMATIS STREET
 WEST PALM BEACH, FL 33401
 PHONE: 494-1040 EXT: 1096
 FAX: 494-1116
 E-MAIL: [email protected]
  
 *********************************************
  
 MANUEL JULIAN GONZALEZ
 ENGINEERING PROJECT COORDINATOR
 ENGINEERING SERVICES DEPARTMENT
 401 CLEMATIS STREET, 4TH FLOOR
 WEST PALM BEACH, FL 33401
 (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402)
 MAIN PHONE: (561) 822-1200
 DIRECT: (561) 494-1085
 FAX: (561) 494-1116
 MOBILE: (561) 644-7301
  
 2) THE PERMIT APPLICATION INDICATES THE REPLACE TILE
 FLOOR THROUGH OUT, PLEASE PROVIDE COMPLIANCE WITH;
  
 2A) FBC-B 2010 1207.3 STRUCTURE-BORNE SOUND.
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR
 BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492.
 2B) FBC-B 2010 603.2 EXCEPTION (1) TILE FLOORING
 FLOOR INSULATION PLACED BETWEEN TWO LAYERS OF
 NONCOMBUSTIBLE MATERIALS WITHOUT AN INTERVENING
 AIRSPACE SHALL BE ALLOWED TO HAVE A FLAME SPREAD INDEX
 OF NOT MORE THAN 100.
  
 2C) FBC-B 2010 603.2 EXCEPTION 2 WOOD FLOORS
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200.
  
 FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS
 A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL
 MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A
 MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723.
  
 703.4 NONCOMBUSTIBILITY TESTS.
 THE TESTS INDICATED IN SECTIONS 703.4.1 AND 703.4.2
 SHALL SERVE AS CRITERIA FOR ACCEPTANCE OF BUILDING
 MATERIALS AS SET FORTH IN SECTIONS 602.2, 602.3 AND
 602.4 IN TYPE I, II, III AND IV CONSTRUCTION. THE TERM
 ?NONCOMBUSTIBLE? DOES NOT APPLY TO THE FLAME SPREAD
 CHARACTERISTICS OF INTERIOR FINISH OR TRIM MATERIALS. A
 MATERIAL SHALL NOT BE CLASSIFIED AS A NONCOMBUSTIBLE
 BUILDING CONSTRUCTION MATERIAL IF IT IS SUBJECT TO AN
 INCREASE IN COMBUSTIBILITY OR FLAME SPREAD BEYOND THE
 LIMITATIONS HEREIN ESTABLISHED THROUGH THE EFFECTS OF
 AGE, MOISTURE OR OTHER ATMOSPHERIC CONDITIONS.
  
 3) THE VALUE OF THE PERMIT IS EXTREMLY LOW!!!! W P B
 ADMINISTRTIVE CODE 108.2 SCHEDULE OF PERMIT FEES. ON
 BUILDINGS, STRUCTURES, ELECTRICAL, GAS, MECHANICAL, AND
 PLUMBING SYSTEMS OR ALTERATIONS REQUIRING A PERMIT, A
 FEE FOR EACH PERMIT SHALL BE PAID AS REQUIRED, IN
 ACCORDANCE WITH THE SCHEDULE ESTABLISHED BY THE
 APPLICABLE GOVERNING AUTHORITY.
  
 108.3* BUILDING PERMIT VALUATION.
 IF, IN THE OPINION OF THE BUILDING OFFICIAL, THE
 CLAIMED VALUATION OF BUILDING, ALTERATION, STRUCTURE,
 ELECTRICAL, GAS, MECHANICAL, OR PLUMBING SYSTEMS
 APPEARS TO BE UNDER ESTIMATED ON THE APPLICATION, THE
 PERMIT SHALL BE DENIED. FOR PERMITTING PURPOSES,
 VALUATION OF BUILDINGS AND SYSTEMS SHALL BE TOTAL
 REPLACEMENT PURPOSES, VALUATION OF BUILDINGS AND
 SYSTEMS SHALL BE THE TOTAL REPLACEMENT VALUE TO INCLUDE
 STRUCTURAL, ELECTRICAL, PLUMBING, MECHANICAL, INTERIOR
 FINISHES, NORMAL SITE WORK (EXCAVATION AND BACKFILL FOR
 BUILDINGS), ARCHITECTURAL AND DESIGN FEES, MARKETING
 COST, OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE.
 VALUATION REFRENCES MAY INCLUDE THE LATEST PUBLISHED
 DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES
 (MARSHALL-SWIFT, MEANS, ETC) WITH REGIONAL ADJUSTMENTS
 FOR LOCATION AS PUBLISHED BY THE INTERNATIONAL CODE
 CONGRESS.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  