Plan Review Notes
Plan Review Notes For Permit 14050532
Permit Number 14050532
Review Stop E
Sequence Number 1
Notes
Date Text
2014-05-28 19:51:35APPROVED THE ELECTRICAL REVIEW WITH THE FOLLOWING
 PROVISOS:
 ELECTRICAL PROVISO FOR PERMIT: 140500532
 1. OUTLET PLACEMENT AS INDICATED ON PLANS DOES NOT
 COMPLY WITH THE REQUIREMENTS OF NEC 210.52. FIELD
 VERIFY OUTLET SPACING TO COMPLY WITH WALL, HALLWAY AND
 KITCHEN COUNTER REQUIREMENTS.
 2. CEILING OUTLET BOXES FOR LUMINAIRES SHALL COMPLY
 WITH NEC 314.27 AND BE LISTED TO SUPPORT 50 LBS.
 3. FOR MORE EFFECTIVE ENERGY CONSERVATION, YOU SHOULD
 USE 3 WAY SWITCHING OF LIGHTING WHEREVER POSSIBLE.
 4. PER FBC-R 303.8 YOU SHALL PROVIDE HEATING, THEREFORE
 THE WALL A/C UNITS SHALL BE REVERSIBLE.
 THESE PLANS WERE REVIEWED BY MIKE ALBARRAN, ELECTRICAL
 PLANS EXAMINER
 YOU ARE WELCOME TO REVIEW STATUS OR COMMENTS AT THE
 FOLLOWING LINK:
  
 HTTP://ONESTOPSHOP.WPBGOV.COM/EGOVPLUS/PERMIT/PERM_STAT
 US.ASPX
  
 ENTER YOUR PERMIT NUMBER (SEE SUBJECT LINE OF THIS
 EMAIL FOR YOUR PERMIT #), CLICK ON THE PERMIT NUMBER,
 AND THEN GO TO "PLAN REVIEWS" TO SEE YOUR COMMENTS (TAB
 ABOVE THE SECOND PERMIT INFORMATION).
 AFTER ISSUANCE, PLEASE CHECK YOUR PLAN CAREFULLY FOR
 COMPLIANCE WITH ANY REDLINES, NOTES, PROVISOS, OR OTHER
 PERMIT CONDITIONS.
 FOR FURTHER ASSISTANCE, PLEASE FEEL FREE TO CONTACT ME.
 I CAN BE REACHED AT 561-805-6718 OR
 [email protected]
  