| Plan Review Notes For Permit 14050532 |
| Permit Number |
14050532 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2014-05-28 19:51:35 | APPROVED THE ELECTRICAL REVIEW WITH THE FOLLOWING | | | PROVISOS: | | | ELECTRICAL PROVISO FOR PERMIT: 140500532 | | | 1. OUTLET PLACEMENT AS INDICATED ON PLANS DOES NOT | | | COMPLY WITH THE REQUIREMENTS OF NEC 210.52. FIELD | | | VERIFY OUTLET SPACING TO COMPLY WITH WALL, HALLWAY AND | | | KITCHEN COUNTER REQUIREMENTS. | | | 2. CEILING OUTLET BOXES FOR LUMINAIRES SHALL COMPLY | | | WITH NEC 314.27 AND BE LISTED TO SUPPORT 50 LBS. | | | 3. FOR MORE EFFECTIVE ENERGY CONSERVATION, YOU SHOULD | | | USE 3 WAY SWITCHING OF LIGHTING WHEREVER POSSIBLE. | | | 4. PER FBC-R 303.8 YOU SHALL PROVIDE HEATING, THEREFORE | | | THE WALL A/C UNITS SHALL BE REVERSIBLE. | | | THESE PLANS WERE REVIEWED BY MIKE ALBARRAN, ELECTRICAL | | | PLANS EXAMINER | | | YOU ARE WELCOME TO REVIEW STATUS OR COMMENTS AT THE | | | FOLLOWING LINK: | | | | | | HTTP://ONESTOPSHOP.WPBGOV.COM/EGOVPLUS/PERMIT/PERM_STAT | | | US.ASPX | | | | | | ENTER YOUR PERMIT NUMBER (SEE SUBJECT LINE OF THIS | | | EMAIL FOR YOUR PERMIT #), CLICK ON THE PERMIT NUMBER, | | | AND THEN GO TO "PLAN REVIEWS" TO SEE YOUR COMMENTS (TAB | | | ABOVE THE SECOND PERMIT INFORMATION). | | | AFTER ISSUANCE, PLEASE CHECK YOUR PLAN CAREFULLY FOR | | | COMPLIANCE WITH ANY REDLINES, NOTES, PROVISOS, OR OTHER | | | PERMIT CONDITIONS. | | | FOR FURTHER ASSISTANCE, PLEASE FEEL FREE TO CONTACT ME. | | | I CAN BE REACHED AT 561-805-6718 OR | | | [email protected] | | | |
|