2014-07-10 08:49:18BUILDING REVIEW APPROVED WITH PROVISO:
 1- REVISE ENERGY CALCULATIONS SUBMITTED:
 A) THIS IS NOT A SINGLE FAMILY. IT'S MULTIPLE FAMILY
 RESIDENCE ( SEE DEFINITIONS IN CHAPTER 2 OF ENERGY
 CONSERVATION CODE). REVISE ALL THE INFORMATION ON PAGE
 ONE AS REQUIRED.
 B) ROOF IS NOT FLAT TILE/SLATE. SEE PLANS AND REVISE AS
 REQUIRED.
 C) OWNER/AGENT TO CERTIFY AND DATE BOTTOM OF FORM AS
 REQUIRED BY SEC. 103.2.3.2 OF 2010 FBC-ENERGY
 CONSERVATION.
  
 2- NEW COMMENT:
 ENERGY CALCULATIONS ARE TAKING THE CEILING FAN CREDIT.
 PLANS TO SHOW CEILING FANS AND SIZE IN ALL ROOMS AS
 REQUIRED BY SEC. 405.6.6 AND TABLE 405.6.6 OF 2010
 FBC-ENERGY CONSERVATION.
  
 3- ENGINEER TO REVISE TENANT SEPARATION DETAIL:
 NATIONAL GYPSUM COMPANY INFORMATION SUBMITTED SHOWS WP
 3605 ASSEMBLY WITH NOT INSULATION INCLUDED. NEED
 APPROVED ASSEMBLY THAT INCLUDES THE INSULATION.
 ***NOTE: ASSEMBLY WP 3241 SHOWN ON THE SAME PAGE
 SUBMITTED INCLUDES THE INSULATION. REVISE DETAIL TO
 MATCH WP3605 ASSEMBLY.
  
 4- ENGINEER OF RECORD TO APPROVE DOORS AND WINDOWS
 PRODUCT APPROVALS. SEC. 107.3.4.1 OF CITY AMENDMENTS TO
 FBC.
  
  