| Plan Review Notes For Permit 14050531 |
| Permit Number |
14050531 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2014-07-10 08:49:18 | BUILDING REVIEW APPROVED WITH PROVISO: | | | 1- REVISE ENERGY CALCULATIONS SUBMITTED: | | | A) THIS IS NOT A SINGLE FAMILY. IT'S MULTIPLE FAMILY | | | RESIDENCE ( SEE DEFINITIONS IN CHAPTER 2 OF ENERGY | | | CONSERVATION CODE). REVISE ALL THE INFORMATION ON PAGE | | | ONE AS REQUIRED. | | | B) ROOF IS NOT FLAT TILE/SLATE. SEE PLANS AND REVISE AS | | | REQUIRED. | | | C) OWNER/AGENT TO CERTIFY AND DATE BOTTOM OF FORM AS | | | REQUIRED BY SEC. 103.2.3.2 OF 2010 FBC-ENERGY | | | CONSERVATION. | | | | | | 2- NEW COMMENT: | | | ENERGY CALCULATIONS ARE TAKING THE CEILING FAN CREDIT. | | | PLANS TO SHOW CEILING FANS AND SIZE IN ALL ROOMS AS | | | REQUIRED BY SEC. 405.6.6 AND TABLE 405.6.6 OF 2010 | | | FBC-ENERGY CONSERVATION. | | | | | | 3- ENGINEER TO REVISE TENANT SEPARATION DETAIL: | | | NATIONAL GYPSUM COMPANY INFORMATION SUBMITTED SHOWS WP | | | 3605 ASSEMBLY WITH NOT INSULATION INCLUDED. NEED | | | APPROVED ASSEMBLY THAT INCLUDES THE INSULATION. | | | ***NOTE: ASSEMBLY WP 3241 SHOWN ON THE SAME PAGE | | | SUBMITTED INCLUDES THE INSULATION. REVISE DETAIL TO | | | MATCH WP3605 ASSEMBLY. | | | | | | 4- ENGINEER OF RECORD TO APPROVE DOORS AND WINDOWS | | | PRODUCT APPROVALS. SEC. 107.3.4.1 OF CITY AMENDMENTS TO | | | FBC. | | | | | | |
|