2014-06-09 17:19:32RESIDENTIAL (R3) ALTERATION/RENOVATION BUILDING REVIEW
 COMMENTS.
 CODE: 2010 FBC.
  
 1- PROVIDE ENERGY CALCULATIONS AS REQUIRED BY SEC.
 R101.4.3 OF 2010 FBC-RESIDENTIAL.
  
 2- TENANT SEPARATION DETAIL: PROVIDE TENANT SEPARATION
 ASSEMBLY NUMBER (UL LISTING OR GYPSUM BOARD LISTING)
 USING 2 X 4 WOOD STUDS INSTEAD OF METAL STUDS TO VERIFY
 COMPLIANCE WITH SEC. R302.3 OF 2010 FBC-RESIDENTIAL.
 ASSEMBLY NEEDS TO BE TESTED IN ACCORDANCE WITH ASTM E
 119 OR UL 263.
  
 3- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 DCA RULE 9N-3 FOR:
 A) ROOF SHINGLES.
  
 B) ALL SIMPSON STRUCTURAL CONNECTORS SPECIFIED ON PLANS
 AND DETAILS. FLORIDA PRODUCT APPROVAL NUMBERS SPECIFIED
 ON SHEET D1 ARE NOT CURRENT. NEED FLORIDA PRODUCT
 APPROVAL NUMBERS THAT CORRESPOND TO THE 2010 FBC.
  
 4- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 OF CITY AMENDMENTS TO FBC.
  