| Plan Review Notes For Permit 14050531 |
| Permit Number |
14050531 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2014-06-09 17:19:32 | RESIDENTIAL (R3) ALTERATION/RENOVATION BUILDING REVIEW | | | COMMENTS. | | | CODE: 2010 FBC. | | | | | | 1- PROVIDE ENERGY CALCULATIONS AS REQUIRED BY SEC. | | | R101.4.3 OF 2010 FBC-RESIDENTIAL. | | | | | | 2- TENANT SEPARATION DETAIL: PROVIDE TENANT SEPARATION | | | ASSEMBLY NUMBER (UL LISTING OR GYPSUM BOARD LISTING) | | | USING 2 X 4 WOOD STUDS INSTEAD OF METAL STUDS TO VERIFY | | | COMPLIANCE WITH SEC. R302.3 OF 2010 FBC-RESIDENTIAL. | | | ASSEMBLY NEEDS TO BE TESTED IN ACCORDANCE WITH ASTM E | | | 119 OR UL 263. | | | | | | 3- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY | | | DCA RULE 9N-3 FOR: | | | A) ROOF SHINGLES. | | | | | | B) ALL SIMPSON STRUCTURAL CONNECTORS SPECIFIED ON PLANS | | | AND DETAILS. FLORIDA PRODUCT APPROVAL NUMBERS SPECIFIED | | | ON SHEET D1 ARE NOT CURRENT. NEED FLORIDA PRODUCT | | | APPROVAL NUMBERS THAT CORRESPOND TO THE 2010 FBC. | | | | | | 4- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING | | | (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS | | | REQUIRED BY SEC. 107.3.4.1 OF CITY AMENDMENTS TO FBC. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CALL | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | DEVELOPMENT SERVICES DEPARTMENT | | | (561)805-6712 |
|