| 2014-05-22 12:50:56 | ELECTRICAL PLAN REVIEW HAS BEEN FOUND TO BE DEFICIENT | | | IN THE AREAS LISTED BELOW. COMPLIANCE SHALL BE BASED ON | | | THE 2008 NEC, THE 2010 FBC, AND THE 2007 NFPA 72 | | | | | | 1) SMOKE DETECTORS ARE INDICATED ON THE FLOOR PLAN BUT | | | NOT ON THE RISER DIAGRAM. THE SMOKE DETECTORS WILL HAVE | | | TO TIE TO THE EXISTING FACP. PLEASE INDICATE WITH A | | | LINE DIAGRAM HOW THIS WILL BE ACCOMPLISHED. | | | | | | 2) THE SMOKE DETECTORS SHALL BE COMPATABLE TO THE | | | EXISTING FACP. PLEASE INDICATE ON THE PLAN THE | | | MANUFACTURER OF THE FACP AND SUBMIT SUPPORTING | | | DOCUMENTATION INDICATING COMPATABILITY. |
|