| 2014-07-01 10:35:51 | DATE: 7/1/2014 | | | PROJECT: OAKTON COMMONS CHARTER SCHOOL | | | PERMIT#: 14050490 | | | CODE: 2008 EDITION OF THE NEC | | | 2010 EDITION OF THE FBC | | | 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, | | | ADMINISTRATION, 2012 FBC SUPPLEMENTS. | | | | | | 1ST ELECTRICAL PLAN REVIEW | | | ACTION: PROVISO | | | | | | 1) THE PLANS INDICATE THE USE OF A TIME CLOCK TO | | | CONTROL A LIGHTING CONTACTOR. WHEN USING A TIME CLOCK | | | INDICATE THE MINIMUM 10HR REQUIRED PROGRAM BACKUP TIME. | | | FBC 505.2.4 | | | | | | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421. | | | 561-805-6717 OR [email protected] |
|