2014-05-29 14:40:41FAILED
  
 1) THE OAKTON COMMONS DESIGN GUIDELINES SPECIFY, "ALL
 OUTDOOR LIGHTING FIXTURES SHALL NOT EXCEED TWENTY-FIVE
 (25) FEET IN HEIGHT, MEASURED FORM FINISHED GRADE TO
 HIGHEST POINT." THE LIGHT POLE STRUCTURE DETAIL SHOWS
 AN EXTENSION (THE ACTUAL LIGHT?) EXCEEDING THE 25 FOOT
 MEASURE POINT.
  
 2) THE CITY'S PLANNED DEVELOPMENT REGULATIONS SPECIFY
 THAT THE LIGHT LEVEL SHALL NOT EXCEED ONE (1) FOOT
 CANDLE AT OR BEYOND THE PROPERTY LINE. THE PHOTOMETRIC
 CALCULATIONS SHALL BE SHOWN AT THE PROPERTY LINE ALONG
 THE OKEECHOBEE BOULEVARD PROPERTY LINE AND SHALL NOT
 EXCEED ONE (1) FOOT CANDLE.
  
 3) THE LIGHT POLES THEMSELVES ARE IN APPROVED
 LOCATIONS.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446.