| Notes |
| Date |
Text |
| 2014-05-14 09:07:58 | ELECTRICAL PROVISO: | | | | | | PLEASE BE SURE TO SEE 2010 FBC SECTION 505.2.4 FOR | | | EXTERIOR LIGHTING CONTROLS REQUIRED. THERE ARE ONE OF | | | TWO METHODS PERMITTED FOR CONTROLS. YOUR PLANS INDICATE | | | THE USE OF A TIME CLOCK TO CONTROL | | | A LIGHTING CONTACTOR. IF USING A TIME CLOCK PLEASE BE | | | SURE TO LIST THE MINIMUM REQUIRED PROGRAMMING BATTERY | | | BACKUP TIME. THE CODE REQUIRES 10HRS MINIMUM | | | | | | | | | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421. | | | 561-805-6717 OR [email protected] |
|