Plan Review Notes
Plan Review Notes For Permit 14050490
Permit Number 14050490
Review Stop E
Sequence Number 1
Notes
Date Text
2014-05-14 09:07:58ELECTRICAL PROVISO:
  
  PLEASE BE SURE TO SEE 2010 FBC SECTION 505.2.4 FOR
 EXTERIOR LIGHTING CONTROLS REQUIRED. THERE ARE ONE OF
 TWO METHODS PERMITTED FOR CONTROLS. YOUR PLANS INDICATE
 THE USE OF A TIME CLOCK TO CONTROL
 A LIGHTING CONTACTOR. IF USING A TIME CLOCK PLEASE BE
 SURE TO LIST THE MINIMUM REQUIRED PROGRAMMING BATTERY
 BACKUP TIME. THE CODE REQUIRES 10HRS MINIMUM
  
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421.
 561-805-6717 OR [email protected]