| 2014-06-04 10:13:52 | PLUMBING PLAN REVIEW |
| | PERMIT: 14050473 |
| | ADD: 1815 PALM BCH LAKES SUITE # SHELL BUILDING "E" |
| | CONT: BRV CONSTRUCTION |
| | TEL: (305)283-7953 |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | 1ST REVIEW |
| | DATE: FRIDAY MAY 30/2014 |
| | ACTION: DENIED |
| | |
| | 1) THE PERMIT APPLICATION & PLANS IDENTIFY THE LOCATION |
| | AS THE OVER ALL SITE ADDRESS OF THE PLAM BEACH OUTLET |
| | MALL, EACH BUILDING AND TENANT SPACE HAS THEIR OWN |
| | INDIVIDUAL ADDRESS, PLEASE CORRECT ONCE THIS IS KNOWN. |
| | |
| | 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING |
| | CODE, CHAPTER 1, ADMINISTRATION, 107.2.1 INFORMATION ON |
| | CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS SHALL BE |
| | OF SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE |
| | AND EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT |
| | IT WILL CONFORM TO THE PROVISIONS OF THIS CODE AND |
| | RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS |
| | DETERMINED BY THE BUILDING OFFICIAL. |
| | |
| | 2010 FBC-B [F] 501.2 ADDRESS IDENTIFICATION. NEW AND |
| | EXISTING BUILDINGS SHALL BE PROVIDED WITH APPROVED |
| | ADDRESS NUMBERS OR LETTERS. |
| | |
| | 2) SHEET P-112 INDICATES THE UNDERGROUND GREASY WASTE |
| | WAS UNDER THE SHELL PERMIT. PLEASE PROVIDE THE METHOD |
| | FOR SIZING OF THE GREASE INTERCEPTOR, IF A CONCRETE |
| | VAULT TYPE THE SIZING METHOD IS SIZED USING THE FORMULA |
| | FOUND IN 2010 FBC-PLUMBING TABLE 1003.5.1. TO DATE |
| | THERE HAS BEEN NO GREASE INTERCEPTOR PERMIT PULLED FOR |
| | THIS SHELL BUILDING. NOTE THERE ARE OTHER SUITES THAT |
| | WILL BE SHARING THIS INTERCEPTOR AS SHOWN SO SIZING |
| | WILL BE RATHER DIFFICULT TO DETERMINE. PLEASE NOTE WE |
| | HAVE SEEN ON OTHER OUT BUILDINGS WHERE THE SITE WORK |
| | WAS REVIEWED BY THE ENGINEERING DEPARTMENT IT WOULDN'T |
| | HAVE BEEN REVIEWED BY THE BUILDING DIVION PLUMBING. |
| | THIS HAS BEEN ISSUES WITH OTHER RESTARAUNTS WHERE THE |
| | GREASE INTERCEPTOR WAS BEING PROVIDED BY THE |
| | LANDLORD!!!!!! THE ENGINEERING REQUIREMENTS ARE NOT AS |
| | STRINGENT AS THE PLUMBING CODE AND HAS BECOME A PROBLEM |
| | FOR THE TENANT FIT UPS REQUIRING THE USE OF GREASE |
| | INTERCEPTORS. |
| | GREASE INTERCEPTORS DO REQUIRE A SEPARATE PERMIT AND |
| | REVIEW, FOR TRACKING PURPOSES FOR THE UTILITY FOG |
| | (FATS, OILS & GREASES) INSPECTORS. |
| | |
| | 3) SHEET P-112 INDICATES THER TO BE A SINGLE UNISEX |
| | RESTROOM, PLEASE REVIEW 2010 FBC-PLUMBING SECTION 403.2 |
| | EXCEPTION # 2 . SEPARATE FACILITIES SHALL NOT BE |
| | REQUIRED FOR FOOD SERVICE ESTABLISHMENTS WHICH SEAT 10 |
| | PERSONS OR LESS. EXCEPTION # 3 IS FOR GENERAL |
| | MERCANTILE OCCUPANCIES, THE EXCEPTION # 2 IS SPECIFIC |
| | TO FOOD SERVICE ESTABLISHMENTS. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |