Plan Review Notes
Plan Review Notes For Permit 14050473
Permit Number 14050473
Review Stop P
Sequence Number 1
Notes
Date Text
2014-06-04 10:13:52PLUMBING PLAN REVIEW
 PERMIT: 14050473
 ADD: 1815 PALM BCH LAKES SUITE # SHELL BUILDING "E"
 CONT: BRV CONSTRUCTION
 TEL: (305)283-7953
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 1ST REVIEW
 DATE: FRIDAY MAY 30/2014
 ACTION: DENIED
  
 1) THE PERMIT APPLICATION & PLANS IDENTIFY THE LOCATION
 AS THE OVER ALL SITE ADDRESS OF THE PLAM BEACH OUTLET
 MALL, EACH BUILDING AND TENANT SPACE HAS THEIR OWN
 INDIVIDUAL ADDRESS, PLEASE CORRECT ONCE THIS IS KNOWN.
  
 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION, 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS SHALL BE
 OF SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE
 AND EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT
 IT WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILDING OFFICIAL.
  
 2010 FBC-B [F] 501.2 ADDRESS IDENTIFICATION. NEW AND
 EXISTING BUILDINGS SHALL BE PROVIDED WITH APPROVED
 ADDRESS NUMBERS OR LETTERS.
  
 2) SHEET P-112 INDICATES THE UNDERGROUND GREASY WASTE
 WAS UNDER THE SHELL PERMIT. PLEASE PROVIDE THE METHOD
 FOR SIZING OF THE GREASE INTERCEPTOR, IF A CONCRETE
 VAULT TYPE THE SIZING METHOD IS SIZED USING THE FORMULA
 FOUND IN 2010 FBC-PLUMBING TABLE 1003.5.1. TO DATE
 THERE HAS BEEN NO GREASE INTERCEPTOR PERMIT PULLED FOR
 THIS SHELL BUILDING. NOTE THERE ARE OTHER SUITES THAT
 WILL BE SHARING THIS INTERCEPTOR AS SHOWN SO SIZING
 WILL BE RATHER DIFFICULT TO DETERMINE. PLEASE NOTE WE
 HAVE SEEN ON OTHER OUT BUILDINGS WHERE THE SITE WORK
 WAS REVIEWED BY THE ENGINEERING DEPARTMENT IT WOULDN'T
 HAVE BEEN REVIEWED BY THE BUILDING DIVION PLUMBING.
 THIS HAS BEEN ISSUES WITH OTHER RESTARAUNTS WHERE THE
 GREASE INTERCEPTOR WAS BEING PROVIDED BY THE
 LANDLORD!!!!!! THE ENGINEERING REQUIREMENTS ARE NOT AS
 STRINGENT AS THE PLUMBING CODE AND HAS BECOME A PROBLEM
 FOR THE TENANT FIT UPS REQUIRING THE USE OF GREASE
 INTERCEPTORS.
 GREASE INTERCEPTORS DO REQUIRE A SEPARATE PERMIT AND
 REVIEW, FOR TRACKING PURPOSES FOR THE UTILITY FOG
 (FATS, OILS & GREASES) INSPECTORS.
  
 3) SHEET P-112 INDICATES THER TO BE A SINGLE UNISEX
 RESTROOM, PLEASE REVIEW 2010 FBC-PLUMBING SECTION 403.2
 EXCEPTION # 2 . SEPARATE FACILITIES SHALL NOT BE
 REQUIRED FOR FOOD SERVICE ESTABLISHMENTS WHICH SEAT 10
 PERSONS OR LESS. EXCEPTION # 3 IS FOR GENERAL
 MERCANTILE OCCUPANCIES, THE EXCEPTION # 2 IS SPECIFIC
 TO FOOD SERVICE ESTABLISHMENTS.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  