Plan Review Notes
Plan Review Notes For Permit 14050471
Permit Number 14050471
Review Stop E
Sequence Number 1
Notes
Date Text
2014-05-15 09:38:28ELECTRICAL PROVISO FOR 14050471
 ALL CONDUCTORS IN CONDUIT EXPOSED TO DIRECT SUNLIGHT
 SHALL BE ADJUSTED ACCORDING TO THE REQUIREMENTS OF NEC
 310.15 & TABLE 310.15(B)(2)(C)
  