| Date |
Text |
| 2014-06-11 11:02:35 | AFTER DISCUSSING THE DIFFERENCES OF THE PLANS WITH THE |
| | ELECTRICAL CONTRACTOR THIS AFTERNOON, THE ELECTRICAL |
| | REVIEW AS PREVIOUSLY NOTED IS BEING APPROVED. I HAVE |
| | THEREFORE REVERSED THE FAILED STATUS AND PASSED THE |
| | APPLICATION. |
| 2014-05-21 15:03:51 | INITIALLY I REVIEWED THE PLANS AS IF THIS WAS A NEW |
| | PERMIT. LATER REALIZED THAT THIS IS A REVISION TO AN |
| | EXISTING MASTER AND NOTICED THE DIFFERENT LAYOUT, THE |
| | SUBMITTED PLANS DO NOT MATCH THE PLANS ON FILE FOR THE |
| | MASTER PERMIT. YOU SHALL PROVIDE PLANS THAT ARE SITE |
| | SPECIFIC. |
| 2014-05-21 14:15:49 | FIRST REVIEW FOR PERMIT # 14050463 |
| | SINCE NO CHANGES TO THE ORIGINAL FOOTPRINT OR |
| | ADDITIONAL LOADS ARE BEING ADDED, LOAD CALCULATIONS |
| | WILL NOT BE REQUIRED, BUT THE FOLLOWING PROVISOS SHALL |
| | BE ADHERED TO: |
| | 1. THE RELOCATED STAIRWAY SHALL BE ILLUMINATED AS |
| | REQUIRED BY NEC 210.70 (A) 2 C. |
| | 2. THE NEW PORCH SHALL HAVE THE LIGHT REQUIRED IN NEC |
| | 210.70, AND THE OUTLET REQUIRED IN 210.52. THE OUTLET |
| | SHALL BE GFCI PROTECTED AS IN 210.8 AND WEATHER |
| | RESISTANT AS IN 406.8. |
| | 3. THERE ARE ADDITIONAL MISSING OUTLETS AS PER NEC |
| | 210.52 THAT SHALL BE INSTALLED AS PART OF THE NEW |
| | CONSTRUCTION. |
| | 4. THE CEILING OUTLETS SHALL COMPLY W/NEC 314.27 AND BE |
| | CAPABLE OF SUPPORTING 50#?S. |
| | 5. ALL NEW WIRING SHALL COMPLY W/NEC 210.12 W/ARC-FAULT |
| | PROTECTION AND NEC 406.11 W/TAMPER-RESISTANT DEVICES. |
| | 6. SMOKER DETECTORS SHALL BE INSTALLED AS PER FBC-R 314 |
| | & 315 IF NOT ALREADY IN PLACE. |
| | THESE PLANS WERE REVIEWED BY MIKE ALBARRAN, ELECTRICAL |
| | PLANS EXAMINER |
| | YOU ARE WELCOME TO REVIEW STATUS OR COMMENTS AT THE |
| | FOLLOWING LINK: |
| | |
| | HTTP://ONESTOPSHOP.WPBGOV.COM/EGOVPLUS/PERMIT/PERM_STAT |
| | US.ASPX |
| | |
| | ENTER YOUR PERMIT NUMBER (SEE SUBJECT LINE OF THIS |
| | EMAIL FOR YOUR PERMIT #), CLICK ON THE PERMIT NUMBER, |
| | AND THEN GO TO "PLAN REVIEWS" TO SEE YOUR COMMENTS (TAB |
| | ABOVE THE SECOND PERMIT INFORMATION). |
| | AFTER ISSUANCE, PLEASE CHECK YOUR PLAN CAREFULLY FOR |
| | COMPLIANCE WITH ANY REDLINES NOTES, PROVISOS, OR OTHER |
| | PERMIT CONDITIONS. |
| | FOR FURTHER ASSISTANCE, PLEASE FEEL FREE TO CONTACT ME. |