2014-05-16 13:29:101ST REVIEW:
  
 THE PLAN REFERENCES THE 2007 FLORIDA BUILDING CODE AS
 THE CODE IN EFFECT. PLEASE REVISE TO THE ACTUAL CODE IN
 EFFECT WHICH IS 2010. THIS IS IN THE MECHAAANICAL
 GENERAL NOTES AND ON PAGE 6.
  
 PER FBC-R-M 1602.4 PROVIDE BALANCED AIR RETURN AT
 BEDROOMS.
  
 INDICATE THE R-VALUE PROPOSED FOR THE DUCT SYSTEM,
 PLEASE NOTE THE MINIMUM PERSCRIPTIVE VALUE IS R-6 PER
 FBC-EC:T402.1.1
  