Plan Review Notes
Plan Review Notes For Permit 14050421
Permit Number 14050421
Review Stop E
Sequence Number 2
Notes
Date Text
2014-07-17 15:03:43PROJECT: PUBLIX #1497 VILLAGE COMMONS, 831 VILLAGE BLVD
 PERMIT#: 14050421
 CODE: 2008 EDITION OF THE NEC.
 2010 EDITION OF THE FBC,
 2010 EDITION OF THE WPB AMENDMENTS TO THE FBC, CHAPTER
 1, ADMINISTRATION
 2ND ELECTRICAL REVIEW
 ACTION: ELECTRICAL PROVISO:
  
 1) DEMONSTRATE COMPLIANCE WITH CALCULATION AND
 CIRCUITRY FOR ALL TRACK LIGHTING LOAD. NEC 220.43(B)
  
 2) DEMONSTRATE COMPLIANCE WITH INSTALLATION OF THE ATM
 MACHINE PER FBC-3112.2 AS FOLLOWS:
 EACH OPERATOR, OR OTHER PERSON RESPONSIBLE FOR AN
 AUTOMATED TELLER MACHINE PURSUANT TO SECTIONS 655.960
 THROUGH 655.965, SHALL PROVIDE LIGHTING DURING THE
 HOURS OF DARKNESS WITH RESPECT TO AN OPEN AND OPERATING
 AUTOMATED TELLER MACHINE AND ANY DEFINED PARKING AREA,
 ACCESS AREA AND THE EXTERIOR OF AN ENCLOSED AUTOMATED
 TELLER MACHINE INSTALLATION, AS FOLLOWS:
  
 THERE SHALL BE A MINIMUM OF 10 FOOT CANDLE (108 LUX)
 POWER AT THE FACE OF THE AUTOMATED TELLER MACHINE AND
 EXTENDING IN AN UNOBSTRUCTED DIRECTION OUTWARD 5 FEET
 (1.5 M).
  
 THERE SHALL BE A MINIMUM OF 2 FOOT CANDLE (21.5 LUX)
 POWER WITHIN 50 FEET (15.25 M) IN ALL UNOBSTRUCTED
 DIRECTIONS FROM THE FACE OF THE AUTOMATED TELLER
 MACHINE. IF THE AUTOMATED TELLER MACHINE IS LOCATED
 WITHIN 10 FEET (3 M) OF THE CORNER OF THE BUILDING AND
 THE AUTOMATED TELLER MACHINE IS GENERALLY ACCESSIBLE
 FROM THE ADJACENT SIDE, THERE SHALL BE A MINIMUM OF 2
 FOOT CANDLE (21.5 LUX) POWER ALONG THE FIRST 40
 UNOBSTRUCTED FEET (12 M) OF THE ADJACENT SIDE OF THE
 BUILDING.
  
 THERE SHALL BE A MINIMUM OF 2 FOOT CANDLE (12.5 LUX)
 POWER IN THAT PORTION OF THE DEFINED PARKING AREA
 WITHIN 60 FEET (18 M) OF THE AUTOMATED TELLER MACHINE.
  
 THE OPERATOR SHALL PROVIDE REFLECTIVE MIRRORS OR
 SURFACES AT EACH AUTOMATED TELLER MACHINE WHICH PROVIDE
 THE CUSTOMER WITH A REAR VIEW WHILE THE CUSTOMER IS
 ENGAGED IN USING THE AUTOMATED TELLER MACHINE.
  
 THE OPERATOR, OR OTHER PERSON RESPONSIBLE PURSUANT TO
 SECTIONS 655.960 THROUGH 655.965 FOR AN AUTOMATED
 TELLER MACHINE, SHALL ENSURE THAT THE HEIGHT OF ANY
 LANDSCAPING, VEGETATION OR OTHER PHYSICAL OBSTRUCTIONS
 IN THE AREA REQUIRED TO BE LIGHTED PURSUANT TO SECTION
 (2) FOR ANY OPEN AND OPERATING AUTOMATED TELLER MACHINE
 SHALL NOT EXCEED 3 FEET (914 MM), EXCEPT THAT TREES
 TRIMMED TO A HEIGHT OF 10 FEET (3 M) AND WHOSE
 DIAMETERS ARE LESS THAN 2 FEET (610 MM) AND MANMADE
 PHYSICAL OBSTRUCTIONS REQUIRED BY STATUTE, LAW, CODE,
 ORDINANCE OR OTHER GOVERNMENTAL REGULATION SHALL NOT BE
 AFFECTED BY THIS SECTION.
  
 3) A PERMANENT PLAQUE OR DIRECTORY, DENOTING ALL
 ELECTRIC POWER SOURCES ON OR IN THE PREMISES, SHALL BE
 INSTALLED AT EACH SERVICE EQUIPMENT LOCATION AND AT
 LOCATIONS OF ALL ELECTRIC POWER PRODUCTION SOURCES
 CAPABLE OF BEING INTERCONNECTED. A SIGN SHALL BE PLACED
 AT THE SERVICE ENTRANCE INDICATING TYPE AND LOCATION OF
 ON-SITE LEGALLY REQUIRED STANDBY POWER SOURCES. NEC
 700, 701.9, AND 705.10
  
 SITE LIGHTING REVIEW 7/17/14 SEE NEC 410.130(G)(2) AND
 (3) BELOW:
 WHEN CONNECTED TO MULTIWIRE BRANCH CIRCUITS, THE
 DISCONNECTING MEANS SHALL SIMULTANEOUSLY BREAK ALL THE
 SUPPLY CONDUCTORS TO THE BALLAST, INCLUDING THE
 GROUNDED CONDUCTOR. NEC 410.130(G)(2)
  
 THE DISCONNECTING MEANS SHALL BE LOCATED SO AS TO BE
 ACCESSIBLE TO QUALIFIED PERSONS BEFORE SERVICING OR
 MAINTAINING THE BALLAST. WHERE THE DISCONNECTING MEANS
 IS EXTERNAL TO THE LUMINAIRE, IT SHALL BE A SINGLE
 DEVICE, AND SHALL BE ATTACHED TO THE LUMINAIRE OR THE
 LUMINAIRE SHALL BE LOCATED WITHIN SIGHT OF THE
 DISCONNECTING MEANS. NEC 410.130(3)
  
 SEPARATE PERMITS SHOP DRAWINGS ETC... FOR VARIOUS
 SCOPES NOT A PART OF THIS PERMIT SUCH AS BUT NOT
 LIMITED TO, SECURITY, FIRE ALARM, CCTV,
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER PX3421,
 561-805-6717, [email protected]