| 2014-07-17 15:03:43 | PROJECT: PUBLIX #1497 VILLAGE COMMONS, 831 VILLAGE BLVD |
| | PERMIT#: 14050421 |
| | CODE: 2008 EDITION OF THE NEC. |
| | 2010 EDITION OF THE FBC, |
| | 2010 EDITION OF THE WPB AMENDMENTS TO THE FBC, CHAPTER |
| | 1, ADMINISTRATION |
| | 2ND ELECTRICAL REVIEW |
| | ACTION: ELECTRICAL PROVISO: |
| | |
| | 1) DEMONSTRATE COMPLIANCE WITH CALCULATION AND |
| | CIRCUITRY FOR ALL TRACK LIGHTING LOAD. NEC 220.43(B) |
| | |
| | 2) DEMONSTRATE COMPLIANCE WITH INSTALLATION OF THE ATM |
| | MACHINE PER FBC-3112.2 AS FOLLOWS: |
| | EACH OPERATOR, OR OTHER PERSON RESPONSIBLE FOR AN |
| | AUTOMATED TELLER MACHINE PURSUANT TO SECTIONS 655.960 |
| | THROUGH 655.965, SHALL PROVIDE LIGHTING DURING THE |
| | HOURS OF DARKNESS WITH RESPECT TO AN OPEN AND OPERATING |
| | AUTOMATED TELLER MACHINE AND ANY DEFINED PARKING AREA, |
| | ACCESS AREA AND THE EXTERIOR OF AN ENCLOSED AUTOMATED |
| | TELLER MACHINE INSTALLATION, AS FOLLOWS: |
| | |
| | THERE SHALL BE A MINIMUM OF 10 FOOT CANDLE (108 LUX) |
| | POWER AT THE FACE OF THE AUTOMATED TELLER MACHINE AND |
| | EXTENDING IN AN UNOBSTRUCTED DIRECTION OUTWARD 5 FEET |
| | (1.5 M). |
| | |
| | THERE SHALL BE A MINIMUM OF 2 FOOT CANDLE (21.5 LUX) |
| | POWER WITHIN 50 FEET (15.25 M) IN ALL UNOBSTRUCTED |
| | DIRECTIONS FROM THE FACE OF THE AUTOMATED TELLER |
| | MACHINE. IF THE AUTOMATED TELLER MACHINE IS LOCATED |
| | WITHIN 10 FEET (3 M) OF THE CORNER OF THE BUILDING AND |
| | THE AUTOMATED TELLER MACHINE IS GENERALLY ACCESSIBLE |
| | FROM THE ADJACENT SIDE, THERE SHALL BE A MINIMUM OF 2 |
| | FOOT CANDLE (21.5 LUX) POWER ALONG THE FIRST 40 |
| | UNOBSTRUCTED FEET (12 M) OF THE ADJACENT SIDE OF THE |
| | BUILDING. |
| | |
| | THERE SHALL BE A MINIMUM OF 2 FOOT CANDLE (12.5 LUX) |
| | POWER IN THAT PORTION OF THE DEFINED PARKING AREA |
| | WITHIN 60 FEET (18 M) OF THE AUTOMATED TELLER MACHINE. |
| | |
| | THE OPERATOR SHALL PROVIDE REFLECTIVE MIRRORS OR |
| | SURFACES AT EACH AUTOMATED TELLER MACHINE WHICH PROVIDE |
| | THE CUSTOMER WITH A REAR VIEW WHILE THE CUSTOMER IS |
| | ENGAGED IN USING THE AUTOMATED TELLER MACHINE. |
| | |
| | THE OPERATOR, OR OTHER PERSON RESPONSIBLE PURSUANT TO |
| | SECTIONS 655.960 THROUGH 655.965 FOR AN AUTOMATED |
| | TELLER MACHINE, SHALL ENSURE THAT THE HEIGHT OF ANY |
| | LANDSCAPING, VEGETATION OR OTHER PHYSICAL OBSTRUCTIONS |
| | IN THE AREA REQUIRED TO BE LIGHTED PURSUANT TO SECTION |
| | (2) FOR ANY OPEN AND OPERATING AUTOMATED TELLER MACHINE |
| | SHALL NOT EXCEED 3 FEET (914 MM), EXCEPT THAT TREES |
| | TRIMMED TO A HEIGHT OF 10 FEET (3 M) AND WHOSE |
| | DIAMETERS ARE LESS THAN 2 FEET (610 MM) AND MANMADE |
| | PHYSICAL OBSTRUCTIONS REQUIRED BY STATUTE, LAW, CODE, |
| | ORDINANCE OR OTHER GOVERNMENTAL REGULATION SHALL NOT BE |
| | AFFECTED BY THIS SECTION. |
| | |
| | 3) A PERMANENT PLAQUE OR DIRECTORY, DENOTING ALL |
| | ELECTRIC POWER SOURCES ON OR IN THE PREMISES, SHALL BE |
| | INSTALLED AT EACH SERVICE EQUIPMENT LOCATION AND AT |
| | LOCATIONS OF ALL ELECTRIC POWER PRODUCTION SOURCES |
| | CAPABLE OF BEING INTERCONNECTED. A SIGN SHALL BE PLACED |
| | AT THE SERVICE ENTRANCE INDICATING TYPE AND LOCATION OF |
| | ON-SITE LEGALLY REQUIRED STANDBY POWER SOURCES. NEC |
| | 700, 701.9, AND 705.10 |
| | |
| | SITE LIGHTING REVIEW 7/17/14 SEE NEC 410.130(G)(2) AND |
| | (3) BELOW: |
| | WHEN CONNECTED TO MULTIWIRE BRANCH CIRCUITS, THE |
| | DISCONNECTING MEANS SHALL SIMULTANEOUSLY BREAK ALL THE |
| | SUPPLY CONDUCTORS TO THE BALLAST, INCLUDING THE |
| | GROUNDED CONDUCTOR. NEC 410.130(G)(2) |
| | |
| | THE DISCONNECTING MEANS SHALL BE LOCATED SO AS TO BE |
| | ACCESSIBLE TO QUALIFIED PERSONS BEFORE SERVICING OR |
| | MAINTAINING THE BALLAST. WHERE THE DISCONNECTING MEANS |
| | IS EXTERNAL TO THE LUMINAIRE, IT SHALL BE A SINGLE |
| | DEVICE, AND SHALL BE ATTACHED TO THE LUMINAIRE OR THE |
| | LUMINAIRE SHALL BE LOCATED WITHIN SIGHT OF THE |
| | DISCONNECTING MEANS. NEC 410.130(3) |
| | |
| | SEPARATE PERMITS SHOP DRAWINGS ETC... FOR VARIOUS |
| | SCOPES NOT A PART OF THIS PERMIT SUCH AS BUT NOT |
| | LIMITED TO, SECURITY, FIRE ALARM, CCTV, |
| | |
| | DAVID HAYES, ELECTRICAL PLANS EXAMINER PX3421, |