| 2014-06-11 09:28:15 | PLUMBING PLAN REVIEW |
| | PERMIT: 14050421 |
| | ADD: 831 VILLAGE BLVD. PUBLIX |
| | CONT: WDI |
| | TEL: (561)989-7231 DYLAN FONSECA |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: WED. JUNE 11/ 2014 |
| | ACTION: PLUMBING PROVISO: |
| | |
| | A SEPARATE PERMIT AND REVIEW IS REQUIRED FOR FUEL GAS. |
| | A SEPARATE PERMIT IS REQUIRED FOR GREASE INTERCEPTOR |
| | SEE COMMENTS. |
| | |
| | 1) SHEETS P3 GREASE INTERCEPTOR SIZING & P6 DETAIL # 5 |
| | DEAL WITH THE SIZING OF THE GREASE INTERCEPTOR. SHEET |
| | P3 REFERS TO THE 2010 IPC COMMENTARY SECTION 1003.3.4.1 |
| | FOR THE SIZING METHOD USED. PLEASE NOTE IN READING THE |
| | IPC COMMENTARY ON SECTION 1003.3.4.1 THIS DEALS WITH |
| | THE HYDROMECHANICAL GREASE INTERCEPTORS NOT THE GRAVITY |
| | TYPE OF INTERCEPTORS. THE SIZING FOR A GRAVITY TYPE |
| | INTERCEPTOR IS BASED ON AT LEAST A 30-MINUTE RETENTION |
| | TIME THROUGH THE GREASE INTERCEPTOR VESSEL. PLEASE SEE |
| | THE REQUIREMENTS FOUND UNDER THE 2010 FBC-B ARE |
| | DIFFERENT FROM WHAT THE BASE CODE IPC 2006 CODE. |
| | FLORIDA IS 2 CODE CYCLES BEHIND THE ICC CODES. |
| | |
| | PLEASE SEE THE 2010 FLB-P 1003.3.4 GREASE INTERCEPTORS |
| | AND AUTOMATIC GREASE REMOVAL DEVICES. |
| | GREASE INTERCEPTORS AND AUTOMATIC GREASE REMOVAL |
| | DEVICES SHALL BE SIZED IN ACCORDANCE WITH PDI G101, |
| | ASME A112.14.3 APPENDIX A, OR ASME A112.14.4. GREASE |
| | INTERCEPTORS AND AUTOMATIC GREASE REMOVAL DEVICES SHALL |
| | BE DESIGNED AND TESTED IN ACCORDANCE WITH PDI G101, |
| | ASME A112.14.3 OR ASME A112.14.4. GREASE INTERCEPTORS |
| | AND AUTOMATIC GREASE REMOVAL DEVICES SHALL BE INSTALLED |
| | IN ACCORDANCE WITH THE MANUFACTURER?S INSTRUCTIONS. |
| | EXCEPTION: GREASE INTERCEPTORS THAT ARE SIZED, |
| | CONSTRUCTED AND APPROVED IN ACCORDANCE WITH RULE 64E-6, |
| | FLORIDA ADMINISTRATIVE CODE AND THAT ARE LOCATED |
| | OUTSIDE THE BUILDING SHALL NOT BE REQUIRED TO MEET THE |
| | REQUIREMENTS OF THIS SECTION. |
| | |
| | NOTE THE EXCEPTION FOUND UNDER RULE 64E-6 IS FOR THE |
| | CONCRETE VAULT TYPE OF GREASE INTERCEPTORS THE TABLE TO |
| | BE USED FOR SIZING SUCH INTERCEPTOR TYPE IS TABLE |
| | 1003.5.1 WHICH DEALS WITH RESTARAUNTS AND OTHER |
| | COMMERCIAL KITCHEN ESTABLISHMENTS. EVEN THIS TABLE WILL |
| | NOT TRUELY REFLECT THE USAGE OR GALLONS PER MINUTE OF |
| | FLOW. IT APPEARS A SOLUTION WILL BE TO SUBMIT UNDER |
| | ALTERNANTE MATERIALS, DESIGNS AND METHODS (104.11) TO |
| | THE BUILDING OFFICIAL FOR APPROVAL. THIS WILL NEED TO |
| | BE DONE IN WRITTEN FORM. |
| | |
| | 104.11 ALTERNATIVE MATERIALS, DESIGN AND METHODS OF |
| | CONSTRUCTION AND EQUIPMENT. THE PROVISIONS OF THIS CODE |
| | ARE NOT INTENDED TO PREVENT THE INSTALLATION OF ANY |
| | MATERIAL OR TO ANY DESIGN OR METHOD OF CONSTRUCTION NOT |
| | SPECIFICALLY PRESCRIBED BY THIS CODE, PROVIDED THAT ANY |
| | SUCH ALTERNAT IVE HAS BEEN APPROVED. AN ALTERNATIVE |
| | MATERIAL, DESIGN OR METHOD OF CONSTRUCTION SHALL BE |
| | APPROVED WHERE THE BUILDING OFFICIAL FINDS THAT THE |
| | PROPOSED DESIGN IS SATISFACTORY AND COMPLIES WITH THE |
| | INTENT OF THE PROVISIONS OF THIS CODE, AND THAT THE |
| | MATERIAL, METHOD OR WORK OFFERED IS, FOR THE PURPOSE |
| | INTENDED, AT LEAST THE EQUIVALENT OF THAT PRESCRIBED IN |
| | THIS CODE IN QUALITY, STRENGTH, EFFECTIVENESS, FIRE |
| | RESISTANCE, DURABILITY AND SAFETY. WHEN ALTERNATE LIFE |
| | SAFETY SYSTEMS ARE DESIGNED, THE SFPE ENGINEERING GUIDE |
| | TO PERFORMANCE-BASED FIRE ANALYSIS AND DESIGN OF |
| | BUILDINGS, OR OTHER METHODS APPROVED BY THE BUILDING |
| | OFFICIAL MAY BE USED. THE BUILDING OFFICIAL SHALL |
| | REQUIRE THAT SUFFICIENT EVIDENCE OR PROOF BE SUBMITTED |
| | TO SUBSTANTIATE CLAIM MADE REGARDING THE ALTERNATIVE. |
| | |
| | 104.11.1 RESEARCH REPORTS. SUPPORTING DATA, WHERE |
| | NECESSARY TO ASSIST IN THE APPROVAL OF MATERIALS OR |
| | ASSEMBLIES NOT SPECIFICALLY PROVIDED FOR IN THIS CODE, |
| | SHALL CONSIST OF VALID RESEARCH REPORTS FROM APPROVED |
| | SOURCES. |
| | |
| | 104.11.2 TESTS. WHENEVER THERE IS INSUFFICIENT EVIDENCE |
| | OF COMPLIANCE WITH THE PROVISIONS OF THIS CODE, OR |
| | EVIDENCE THAT A MATERIAL OR METHOD DOES NOT CONFORM TO |
| | THE REQUIREMENTS OF THIS CODE, OR IN ORDER TO |
| | SUBSTANTIATE CLAIMS FOR ALTERNATIVE MATERIALS OR |
| | METHODS, THE BUILDING OFFICIAL SHALL HAVE THE AUTHORITY |
| | TO REQUIRE TESTS AS EVIDENCE OF COMPLIANCE TO BE MADE |
| | AT NO EXPENSE TO THE JURISDICTION. TEST METHODS SHALL |
| | BE AS SPECIFIED IN THIS CODE OR BY OTHER RECOGNIZED |
| | TEST STANDARDS. IN THE ABSENCE OF RECOGNIZED AND |
| | ACCEPTED TEST METHODS, THE BUILDING OFFICIAL SHALL |
| | APPROVE THE TESTING PROCEDURES. TESTS SHALL BE |
| | PERFORMED BY AN APPROVED AGENCY. REPORTS OF SUCH TESTS |
| | SHALL BE RETAINED BY THE BUILDING OFFICIAL FOR THE |
| | PERIOD REQUIRED FOR RETENTION OF PUBLIC RECORDS. |
| | |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | DEVELOPMENT SERVICES HOME PAGE |
| | HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP |
| | |
| | PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS |
| | LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS |
| | REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO |
| | THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE |
| | THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |
| | |
| | MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF |
| | FLORIDA SAVING LIVES AND PROPERTY SINCE 1953 |
| | |
| | |
| | |