| 2014-05-19 10:16:18 | ELECTRIC REVIEW DENIED. ALL DEFICIENCIES BASED ON THE |
| | 2010 FBC AND THE 2008 NEC. |
| | |
| | 1) ADDITIONAL RECEPTACLES MAY BE REQUIRED IN THE LIVING |
| | ROOM. ADD RECEPTACLES SO THAT NO WALL SPACE IS MORE |
| | THAN 6 FEET FROM A RECEPTACLE AND ALL WALL SPACES MORE |
| | THAN 2 FEET IN WIDTH HAVE A RECEPTACLE. NEC 210.52 |
| | |
| | 2) THE RISER DIAGRAM INDICATES A NEW 200AMP MAIN PANEL |
| | INSIDE THE RESIDENCE WITH NO MAIN DISCONNECT INDICATED |
| | NEXT TO THE METER OUTSIDE. THE SERVICE ENTRANCE |
| | DISCONNECTING MEANS SHALL BE INSTALLED TO COMPLY WITH |
| | NEC 230.70. |
| | |
| | 3) PLEASE PROVIDE THE PANEL SCHEDULES AND SHOW CIRCUITS |
| | ON FLOOR PLAN. FBC- 107.3.5.3 |
| | |
| | 4) A BONDING STRIP IS REQUIRED AT SERVICE GROUND NEC |
| | 250.94 |
| | |
| | 5) PROVIDE A GROUNDING ELECTRODE FOR THE GUEST HOUSE |
| | ELECTRIC PANEL AND INDICATE IT ON THE PLANS. NEC 250.32 |
| | |
| | 6) LUMINAIRES IN CLOTHES CLOSETS. ARTICLE 410.16 (C)(3) |
| | LOCATION. STATES IN PART , THE MINIMUM CLEARANCE |
| | BETWEEN LUMINAIRES INSTALLED IN CLOTHES CLOSETS AND THE |
| | NEAREST POINT OF A STORAGE SPACE SHALL BE AS FOLLOWS: |
| | "150MM (6") FOR RECESSED INCANDESCENT OR LED LUMINAIRES |
| | WITH A COMPLETELY ENCLOSED LIGHT SOURCE INSTALLED IN |
| | THE WALL OR CEILING" OR (4) "150MM (6") FOR RECESSED |
| | FLUORESCENT LUMINAIRES INSTALLED IN THE WALL OR |
| | CEILING." PLEASE INDICATE COMPLIANCE WITH THIS SECTION |
| | OF THE NEC WHERE INSTALLING RECESSED LIGHTING IN THE |
| | CLOTHES CLOSET IN THE MASTER BEDROOM. |
| | |
| | 7) BATHROOM GFIC OUTLET. BATHROOM BRANCH CIRCUITS IN |
| | ADDITION TO THE NUMBER OF BRANCH CIRCUITS REQUIRED BY |
| | OTHER PARTS OF THIS SECTION, AT LEAST ONE 20-AMPERE |
| | BRANCH CIRCUIT SHALL BE PROVIDED TO SUPPLY BATHROOM |
| | RECEPTACLE OUTLET(S). SUCH CIRCUITS SHALL HAVE NO OTHER |
| | OUTLETS. THE PLAN SHOWS NEW OUTLET IN THE BATHROOM FOR |
| | A LIGHTED MIRROR. PLEASE INDICATE COMPLIANCE WITH |
| | ARTICLE 210.11 (C)(3) |
| | |
| | 8) REMODELING OF AN EXISTING STRUCTURE IS REQUIRED TO |
| | INCLUDE INTERCONNECTED SMOKE ALARMS BOTH WITHIN AND |
| | OUTSIDE EACH SLEEPING AREA. IF THE RESIDENCE HAS GAS |
| | APPLIANCES, AN ATTACHED GARAGE OR A FIRE PLACE A CARBON |
| | MONOXIDE DETECTOR IS REQUIRED WITHIN TEN FEET OF EACH |
| | ROOM USED FOR SLEEPING. 2010 FBC R314, 315 |
| | |
| | |
| | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, |
| | 561-805-6717 OR AT [email protected] |