| 2014-06-02 14:19:25 | SUPPLEMENTAL COMMENTS |
| | |
| | FBC-107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. ALL |
| | INFORMATION, DRAWINGS, SPECIFICATIONS AND ACCOMPANYING |
| | DATA SHALL BEAR THE NAME AND SIGNATURE OF THE PERSON |
| | RESPONSIBLE FOR THE DESIGN. |
| | |
| | FBC 107.2.1.4 QUALITY OF BUILDING PLANS. BUILDING PLANS |
| | SHALL BE DRAWN TO A MINIMUM 1/8 INCH SCALE UPON |
| | SUBSTANTIAL PAPER, OR OTHER ACCEPTABLE MEDIUM. THE |
| | QUALITY OF THE PLAN IS INSUFFICIENT. |
| | |
| | STEVEN KENNEDY, CBO |
| | CHIEF PLANS EXAMINER |
| | (561) 805-6710 |
| | [email protected] |
| | |
| | |
| | |
| 2014-05-21 16:38:48 | FAILED FIRST REVIEW AS FOLLOWS: |
| | NOT ENOUGH ELECTRICAL INFORMATION FOR A SUCCESSFUL |
| | REVIEW. YOU SHALL PROVIDE A LAYOUT OF THE PROPOSED |
| | KITCHEN WITH CABINETS AND THE REQUIRED OUTLETS MARKED. |
| | YOU SHALL INCLUDE THE REQUIRED NOTES AND APPLICABLE |
| | CODE. |
| | INDICATE IF THE NEW COOK TOP AND DOUBLE OVEN ARE GAS |
| | PROVIDE A PANEL SCHEDULE |
| | |
| | THESE PLANS WERE REVIEWED BY MIKE ALBARRAN, ELECTRICAL |
| | PLANS EXAMINER |
| | YOU ARE WELCOME TO REVIEW STATUS OR COMMENTS AT THE |
| | FOLLOWING LINK: |
| | |
| | HTTP://ONESTOPSHOP.WPBGOV.COM/EGOVPLUS/PERMIT/PERM_STAT |
| | US.ASPX |
| | |
| | ENTER YOUR PERMIT NUMBER (SEE SUBJECT LINE OF THIS |
| | EMAIL FOR YOUR PERMIT #), CLICK ON THE PERMIT NUMBER, |
| | AND THEN GO TO "PLAN REVIEWS" TO SEE YOUR COMMENTS (TAB |
| | ABOVE THE SECOND PERMIT INFORMATION). |
| | AFTER ISSUANCE, PLEASE CHECK YOUR PLAN CAREFULLY FOR |
| | COMPLIANCE WITH ANY REDLINES, NOTES, PROVISOS, OR OTHER |
| | PERMIT CONDITIONS. |
| | FOR FURTHER ASSISTANCE, PLEASE FEEL FREE TO CONTACT ME. |
| | I CAN BE REACHED AT 561-805-6718 OR |
| | [email protected] |
| | |