Plan Review Notes
Plan Review Notes For Permit 14050337
Permit Number 14050337
Review Stop B
Sequence Number 2
Notes
Date Text
2014-05-28 14:50:24****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. SEE FBC 2010 RESIDENTIAL FIGURE 301.2(7),
 EDGE/CORNER ZONE TO BE 4' (3' SPECIFIED ON THE
 ENGINEERING).
  
 2. ASSEMBLY PROPOSED IS NOT CLEAR. CONTRACTOR HAD
 ORIGINALLY INDICATED AN ASSEMBLY WHICH USES RING SHANK
 NAILS AND TIN CAPS AS FASTENERS, -52.5 PSF.
  
 A DIFFERENT ASSEMBLY IS NOW CIRCLED WHICH USES DRILL
 TEC FASTENERS AND PLATES, -45 PSF. ENGINEERING REFERS
 TO -45 PSF LIMITATION, BUT LANGUAGE IN NAILING PATTERN
 REFERS TO "TTAG".
  
 IF CONTRACTOR PROPOSES TO USE THE ASSEMBLY WHICH
 SPECIFIES DRILL TEC FASTNERS/PLATES, NO ACTION
 REQUIRED. IF CONTRACTOR WOULD LIKE TO INSTALL THE
 ASSEMBLY WHICH USES NAILS AND TIN TAGS, REVISE
 ENGINEERING ACCORDINGLY.
  
  