| Notes |
| Date |
Text |
| 2014-05-28 14:50:24 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | 1. SEE FBC 2010 RESIDENTIAL FIGURE 301.2(7), | | | EDGE/CORNER ZONE TO BE 4' (3' SPECIFIED ON THE | | | ENGINEERING). | | | | | | 2. ASSEMBLY PROPOSED IS NOT CLEAR. CONTRACTOR HAD | | | ORIGINALLY INDICATED AN ASSEMBLY WHICH USES RING SHANK | | | NAILS AND TIN CAPS AS FASTENERS, -52.5 PSF. | | | | | | A DIFFERENT ASSEMBLY IS NOW CIRCLED WHICH USES DRILL | | | TEC FASTENERS AND PLATES, -45 PSF. ENGINEERING REFERS | | | TO -45 PSF LIMITATION, BUT LANGUAGE IN NAILING PATTERN | | | REFERS TO "TTAG". | | | | | | IF CONTRACTOR PROPOSES TO USE THE ASSEMBLY WHICH | | | SPECIFIES DRILL TEC FASTNERS/PLATES, NO ACTION | | | REQUIRED. IF CONTRACTOR WOULD LIKE TO INSTALL THE | | | ASSEMBLY WHICH USES NAILS AND TIN TAGS, REVISE | | | ENGINEERING ACCORDINGLY. | | | | | | |
|