| 2014-05-13 11:27:08 | 2010 FBC | | | | | | DENIED BY BUILDING | | | | | | 1) SUBMIT TWO COPIES OF THE MANUFACTURER'S INSTALLATION | | | INSTRUCTIONS FOR THE SAM 3 90 SOUND UNDERLAYMENT. | | | | | | 2) SUBMIT DOCUMENTATION THAT SHOWS THE UNDERLAYMENT | | | COMPLIES WITH FBC 1207.2 FOR AIR BOURNE SOUND (STC OF | | | NOT LESS THAN 50) AND FBC 1207.3 FOR STRUCTURE BOURNE | | | SOUND ( IIC OF NOT LESS THAN 50). | | | | | | 3) SUBMIT DOCUMENTATION THAT SHOWS THAT THE SURFACE | | | BURNING TEST REPORT THAT WAS SUBMITTED IS FOR THE SAM 3 | | | 90 SOUND CONTROL MEMBRANE AND NOT ONE OF THE OTHER | | | PRODUCT PRODUCED BY NAC PRODUCTS INC. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|