| 2014-05-18 09:04:28 | 1ST REVIEW: |
| | |
| | 1) FBC-R-M 1602.4 PROVIDE BALANCED AIR RETURN AT THE |
| | MASTER BEDROOM I DO NOT SEE A RAG OR JUMPER FOR THIS |
| | ROOM ON THE PLAN. |
| | |
| | 2) FBC-EC 403.2.5 PROVIDE A SIZING CALCULATION: PRVIDE |
| | A SIZING CALCULATION THAT IS CONSISTENT WITH THE |
| | INFORMATION ON THE PLAN. THE MANUAL J MODEL NUMBER FOR |
| | SYSTEM 2 DOES NOT MATCH THAT SPECIFIED UPON THE PLAN. |
| | PROVIDE THE SENSIBLE AND LATENT COOLING CAPACITY ON THE |
| | EQUIPMENT SCHEDULE FOR EACH SYSTEM ON THE PLAN. |
| | |
| | 3) FBC-R M1305.1.3 APPLIANCES IN ATTICS. INDICATE ON |
| | THE PLAN THE FOLLOWING, PARTICULARLY THE INTENT TO |
| | PROVIDE SOLID DECKING: ATTICS CONTAINING APPLIANCES |
| | SHALL BE PROVIDED WITH AN OPENING AND A CLEAR AND |
| | UNOBSTRUCTED PASSAGEWAY LARGE ENOUGH TO ALLOW REMOVAL |
| | OF THE LARGEST APPLIANCE, BUT NOT LESS THAN 30 INCHES |
| | (762 MM) HIGH AND 22 INCHES (559 MM) WIDE AND NOT MORE |
| | THAN 6 FEET (1829 MM) LONG MEASURED ALONG THE |
| | CENTERLINE OF THE PASSAGEWAY FROM THE OPENING TO THE |
| | APPLIANCE. THE PASSAGEWAY SHALL HAVE CONTINUOUS SOLID |
| | FLOORING IN ACCORDANCE WITH CHAPTER 5 NOT LESS THAN 24 |
| | INCHES (610 MM) WIDE. A LEVEL SERVICE SPACE AT LEAST 30 |
| | INCHES (762 MM) DEEP AND 30 INCHES (762 MM) WIDE SHALL |
| | BE PRESENT ALONG ALL SIDES OF THE APPLIANCE WHERE |
| | ACCESS IS REQUIRED. THE CLEAR ACCESS OPENING DIMENSIONS |
| | SHALL BE A MINIMUM OF 20 INCHES BY 30 INCHES (508 MM BY |
| | 762 MM), AND LARGE ENOUGH TO ALLOW REMOVAL OF THE |
| | LARGEST APPLIANCE. |
| | |
| | 4) FBC-R M1305.1.3.1 ELECTRICAL REQUIREMENTS. |
| | A LUMINAIRE CONTROLLED BY A SWITCH LOCATED AT THE |
| | REQUIRED PASSAGEWAY OPENING AND A RECEPTACLE OUTLET |
| | SHALL BE INSTALLED AT OR NEAR THE APPLIANCE LOCATION IN |
| | ACCORDANCE WITH CHAPTER 34. |
| | |
| | 5) INDICATE UPON THE PLAN COMPLIANCE WITH #2 & #3 |
| | BELOW: |
| | FBC-R M1305.1.3.2 AIR-HANDLING UNITS AIR-HANDLING UNITS |
| | SHALL BE ALLOWED IN ATTICS IF THE FOLLOWING CONDITIONS |
| | ARE MET: |
| | 1. THE SERVICE PANEL OF THE EQUIPMENT IS LOCATED WITHIN |
| | 6 FEET (1829 MM) OF AN ATTIC ACCESS. |
| | 2. A DEVICE IS INSTALLED TO ALERT THE OWNER OR SHUT THE |
| | UNIT DOWN WHEN THE CONDENSATION DRAIN IS NOT WORKING |
| | PROPERLY. |
| | 3. THE ATTIC ACCESS OPENING IS OF SUFFICIENT SIZE TO |
| | REPLACE THE AIR HANDLER |
| | 4. A NOTICE IS POSTED ON THE ELECTRIC SERVICE PANEL |
| | INDICATING TO THE HOMEOWNER THAT THE AIR HANDLER IS |
| | LOCATED IN THE ATTIC. SAID NOTICE SHALL BE IN ALL |
| | CAPITALS, IN 16 POINT TYPE, WITH THE TITLE AND FIRST |
| | PARAGRAPH IN BOLD: |
| | |