| 2014-05-19 14:22:37 | ELECTRICAL REVIEW DENIED. THE ELECTRICAL SYSTEM IS |
| | FOUND TO BE DEFICIENT IN THE FOLLOWING AREAS BASED ON |
| | 2008 EDITION OF THE NEC AND THE 2010 FBC, FBC RES., FBC |
| | ENERGY, SEE COMMENTS BELOW. |
| | |
| | 1) ELECTRICAL SERVICE RISER INDICATES A 300AMP |
| | DISCONNECT SWITCH WITH A 2/0 FEEDER. THE MINIMUM SIZE |
| | SERVICE ENTRANCE CONDUCTOR FOR A RESIDENTIAL SERVICE |
| | ENTRANCE OR FEEDER IS A 250MCM CU. OR 350MCM AL. |
| | |
| | 2) THE DESIGN OF THE ELECTRICAL SERVICE RISER IS NOT IN |
| | COMPLIANCE WITH NEC 310.15(B)(6), 240.21. PLEASE SHOW |
| | OVER CURRENT PROTECTION AND APPROPRIATE FEEDER SIZE FOR |
| | SUB-PANEL "B" |
| | |
| | 3) GROUNDING ELECTRODE CONDUCTOR APPEARS TO BE |
| | IMPROPERLY SIZED FOR BONDING OF ALL SYSTEMS AND PROVIDE |
| | BONDING OF ALL SYSTEMS AND BUILDING STEEL, AS |
| | APPLICABLE 250.66, 250.104THE GROUNDING ELECTRODE |
| | CONDUCTOR FOR A 300AMP SERVICE IS REQUIRED TO BE A #2CU |
| | MINIMUM. |
| | |
| | 4) AN INTERSYSTEM BOND STRIP IS REQUIRED PER 250.94 |
| | |
| | 5) ALL 125V SINGLE PHASE, 15 AND 20AMP RECEPTACLES |
| | INSTALLED IN THE LOCATIONS SPECIFIED IN (1) THROUGH (8) |
| | SHALL HAVE GROUND FAULT CIRCUIT INTERRUPTER PROTECTION |
| | FOR PERSONNEL. NEC 210.8. ALL OUTLETS IN THE GARAGE |
| | SHALL BE GFCI PROTECTED. |
| | |
| | 6) LUMINAIRES IN CLOTHES CLOSETS. ARTICLE 410.16 (C)(3) |
| | LOCATION. STATES IN PART , THE MINIMUM CLEARANCE |
| | BETWEEN LUMINAIRES INSTALLED IN CLOTHES CLOSETS AND THE |
| | NEAREST POINT OF A STORAGE SPACE SHALL BE AS FOLLOWS: |
| | "150MM (6") FOR RECESSED INCANDESCENT OR LED LUMINAIRES |
| | WITH A COMPLETELY ENCLOSED LIGHT SOURCE INSTALLED IN |
| | THE WALL OR CEILING" OR (4) "150MM (6") FOR RECESSED |
| | FLUORESCENT LUMINAIRES INSTALLED IN THE WALL OR |
| | CEILING." PLEASE INDICATE COMPLIANCE WITH THIS SECTION |
| | OF THE NEC WHERE INSTALLING RECESSED LIGHTING IN |
| | CLOTHES CLOSETS |
| | |
| | 7) RECEPTACLES SHALL BE SPACED SO THAT AT NO POINT |
| | ALONG THE FLOOR IN ANY WALL IS MORE THAN 6 FEET FROM A |
| | RECEPTACLE OUTLET. NEC 210.52 (A)(2). |
| | THERE ARE SEVERAL AREAS THROUGHOUT THE HOME TO BE |
| | ADDRESSED. |
| | |
| | 8) RECESSED LIGHTING TO BE AIR TIGHT AND IC RATED. AT |
| | LEAST 50% OF THE LAMPS IN PERMANENTLY INSTALLED LIGHT |
| | FIXTURES SHALL BE HIGH EFFICIENCY. FBC-R 402.4.5, & |
| | 404.1, |
| | |
| | 9) ALL NEW RECEPTACLES MUST BE TAMPER RESISTANT. NEC |
| | 406.11 THOSE OUTLETS IN WET LOCATIONS SHALL BE WEATHER |
| | RESISTANT NEC 406.8(B)(1) |
| | |
| | 10) OCCUPIABLE BALCONIES AND PORCHES OVER 20 SQ FT MUST |
| | HAVE A RECEPTACLE OUTLET GFCI PROTECTED. NEC |
| | 210.52(E)(3). |
| | |
| | 11) IN KITCHENS, PANTRIES, BREAKFAST ROOMS, DINING |
| | ROOMS, AND SIMILAR AREAS OF DWELLING UNITS, RECEPTACLE |
| | OUTLETS FOR COUNTERTOP SPACES SHALL BE INSTALLED IN |
| | ACCORDANCE WITH NEC 210.52(C)(1) THROUGH (C)(5). |
| | |
| | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, |
| | 561-805-6717 OR AT [email protected] |